Checklist before starting operation

3.5
Checklist before starting operation
The FR-A800 series inverter and converter unit are highly reliable products, but incorrect peripheral circuit making or
operation/handling method may shorten the product life or damage the products.
Before starting operation, always recheck the following points.
Checkpoint
Crimp terminals are insulated.
The wiring between the power
supply (R/L1, S/L2, T/L3) and the
motor (U, V, W) is correct.
No wire offcuts are left from the time
of wiring.
The main circuit cable gauge is
correctly selected.
The total wiring length is within the
specified length.
Countermeasures are taken against
EMI.
Countermeasures are taken against
electrical corrosion on the motor
bearing.
On the inverter's output side, there
is no power factor correction
capacitor, surge suppressor, or
radio noise filter installed.
When performing an inspection or
rewiring on the product that has
been energized, the operator has
waited long enough after shutting off
the power supply.
The inverter's output side has no
short circuit or ground fault
occurring.
The circuit is not configured to use
the converter unit's input-side
magnetic contactor to start/stop the
inverter frequently.
80
PRECAUTIONS FOR USE OF THE INVERTER
Countermeasure
Use crimp terminals with insulation sleeves to wire the power supply and the
motor.
Application of power to the output terminals (U, V, W) of the inverter will
damage the inverter. Never perform such wiring.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the
inverter and the converter unit clean.
When drilling mounting holes in an enclosure etc., take caution not to allow
chips and other foreign matter to enter the inverter and the converter unit.
Use an appropriate cable gauge to suppress the voltage drop to 2% or less.
If the wiring distance is long between the inverter and motor, the voltage drop
in the main circuit will cause the motor torque to decrease especially during
the output of a low frequency.
Keep the total wiring length is within the specified length.
Especially for long-distance wiring, the inverter may be affected by a
charging current caused by the stray capacitances of the wiring, leading to a
malfunction or fault of the equipment connected on the inverter output side.
Pay attention to the total wiring length.
The input/output (main circuit) of the inverter and the converter unit includes
high frequency components, which may interfere with the communication
devices (such as AM radios) used near the inverter and the converter unit. In
such case, enable the built-in EMC filter of the converter unit (connect two of
the EMC filter ON/OFF female connectors to the ON male connectors) to
minimize interference.
When a motor is driven by the inverter, axial voltage is generated on the
motor shaft, which may cause electrical corrosion of the bearing in rare
cases depending on the wiring, load, operating conditions of the motor or
specific inverter settings (EMC filter ON).
Contact your sales representative to take appropriate countermeasures for
the motor.
The following shows examples of countermeasures for the inverter.
• Turn OFF the EMC filter.
• Provide a common mode choke on the output side of the inverter.
effective regardless of the EMC filter ON/OFF connector setting.)
Doing so will cause the inverter output shutoff or the capacitor and surge
suppressor to be damaged. If any of the above devices is connected,
immediately remove it.
For a short time after the power-OFF, a high voltage remains in the
smoothing capacitor, and it is dangerous.
Before performing an inspection or rewiring, wait 10 minutes or longer after
the power supply turns OFF, then confirm that the voltage across the main
circuit terminals P/+ and N/- of the inverter is low enough using a tester, etc.
• A short circuit or earth (ground) fault on the inverter's output side may
damage the inverter module.
• Fully check the insulation resistance of the circuit prior to inverter operation
since repeated short circuits caused by peripheral circuit inadequacy or an
earth (ground) fault caused by wiring inadequacy or reduced motor
insulation resistance may damage the inverter module.
• Fully check the to-earth (ground) insulation and phase-to-phase insulation
of the inverter's output side before power-ON. Especially for an old motor or
use in hostile atmosphere, securely check the motor insulation resistance,
etc.
Since repeated inrush currents at power ON will shorten the life of the
inverter and the converter unit, frequent starts and stops of the magnetic
contactor must be avoided. Turn ON/OFF the inverter's start signals (STF,
STR) to run/stop the inverter.
Refer
Check
to page
by user
-
36
-
37
37
74
-

(This is
-
-
-
78