Selecting the rated sensitivity current for the earth leakage circuit
breaker
When using the earth leakage circuit breaker with the inverter circuit, select its rated sensitivity current as follows.
• Breaker designed for harmonic and surge suppression
Rated sensitivity current
In  10  (Ig1 + Ign + Igi + Ig2 + Igm)
• Standard breaker
Rated sensitivity current
In  10  {Ig1 + Ign + Igi + 3  (Ig2 + Igm)}
<Example>
2
2
5.5 mm
5 m
5.5 mm
ELB
Noise
filter
Inverter
Ig1
Ign
Ig2
Igi
• Leakage current per inverter / converter unit
400 V class (input power condition: 440 V / 60 Hz, power supply unbalance within 3%)
Inverter /
converter unit
(Separated converter type)
EMC filter
Phase
2
earthing
(grounding)
Earthed-neutral
1
system
Electro-magnetic interference (EMI) and leakage currents
• Selection example for the
Leakage current Ig1 (mA)
60 m
Leakage current Ign (mA)
φ3
Leakage current Igi (mA)
M
400 V
2.2 kW
Igm
Leakage current Ig2 (mA)
Motor leakage current Igm (mA)
Total leakage current (mA)
Rated sensitivity current (mA) ( Ig  10) 30
FR-A802-P
-
PRECAUTIONS FOR USE OF THE INVERTER
Ig1, Ig2:
Leakage currents in wire path during commercial
power supply operation
Ign:
Leakage current of inverter input side noise filter
Igm:
Leakage current of motor during commercial power
supply operation
Igi:
Leakage current of inverter unit
(When the converter unit is connected, add the
leakage current of converter unit.)
Example of leakage current per 1 km during
the commercial power supply operation
when the CV cable is routed in metal conduit
(Three-phase three-wire delta
connection 400 V 60 Hz)
120
100
8 0
6 0
4 0
2 0
0
2 3.5
8 1422
38
80
150
5.5
30
60
100
Cable size (mm
2
)
For " " connection, the amount of leakage current is approx. 1/3 of the above value.
connection of the 400 V class
Breaker designed
Item
for harmonic and
surge suppression
0 (without noise filter)
1 (without EMC filter)
For the leakage current of the inverter, refer to
the following table.
0.36
2.79
Converter unit
FR-CC2-P
ON
OFF
70
2
2
1
(mA)
Leakage current example of three-
phase induction motor during the
commercial power supply operation
(Totally-enclosed fan-cooled
type motor 400 V 60 Hz)
2. 0
1. 0
0. 7
0. 5
0. 3
0. 2
0. 1
1. 5 3. 7
7. 5 1522
37
55
2. 2
5.5
11
18. 5
30
45
Motor capacity (kW)
Standard breaker
1
5 m
66 
= 0.11
3
1000 m
1
60 m
66 
= 1.32
3
1000 m
6.15
100
3
69