Communication Connectors And Terminals - Mitsubishi Electric FR-A802-P Instruction Manual

Separated converter type for parallel operation
Table of Contents

Advertisement

2.7

Communication connectors and terminals

2.7.1
RS-485 terminal block
Connecting the RS-485 terminals of the master/slave inverters enables communication for parallel operation.
For wiring, refer to
page
56.
RS-485 terminal layout
Terminating resistor switch
Initially-set to "OPEN".
Set only the terminating resistor switch of
the remotest inverter to the "100Ω" position.
VCC
GND
TXD1+
OPEN
VCC GND
+ TXD
100Ω
VCC GND
+ TXD
VCC
GND
TXD2+
Wiring the RS-485 terminals
• Use a four, twisted-pair wires cable for connection.
• The size of RS-485 terminal block is the same as the control circuit terminal block. Refer to
NOTE
• The length of the individual wires connecting the terminal blocks to each other should not exceed 5 m.
• To avoid malfunction, keep the RS-485 terminal wires away from the control circuit board.
• For wiring of the RS-485 terminals used with a plug-in option, lead the wires on the left side of the plug-in option.
TXD1-
RXD1+
RXD1-
-
+
RXD
-
-
+
RXD
-
TXD2-
RXD2+
RXD2-
Communication connectors and terminals
Name
Description
RXD1+
Inverter receive +
RXD1-
Inverter receive -
RXD2+
Inverter receive + (for branch)
RXD2-
Inverter receive - (for branch)
TXD1+
Inverter send +
TXD1-
Inverter send -
TXD2+
Inverter send + (for branch)
TXD2-
Inverter send - (for branch)
5V
VCC
Permissible load current 100 mA
Earthing (grounding)
GND
(connected to terminal SD)
INSTALLATION AND WIRING
page 47
for the wiring method.