required value (address range is 0-63). press
address value to the indoor unit. In 60 seconds, the wired controller will exit the address
setting page, or press
• In the address setting page, the wired controller will not respond to any remote control signals.
3. Commissioning Parameter Settings
• Commissioning parameter can be set when the unit is on or off.
• Press and hold
commissioning parameter settings.
• Go to the commissioning parameter setting page. Check that "C0" is displayed in the temperature
display area. Press ▲ and ▼ buttons to change the "commissioning parameter Code".
• Once the "commissioning parameter Code" is selected, press
specific commissioning parameter settings, and then press ▲ and ▼ buttons to adjust the value.
Press
(Confirm) button to save the value and complete the commissioning parameter
setting.
• Press
(Cancel) button to return to the previous page until you exit commissioning parameter
settings. Alternatively, system will exit the commissioning parameter settings page if there is no
operation for 60 seconds.
• When it is in the commissioning parameter settings page, the wired controller does not
respond to any remote control signals.
• In the commissioning parameter setting page, the
(Function) and
(Cancel) button to exit the address setting page.
(Function) and
(Mode) buttons for 5 seconds to go to the page for
(ON/OFF) buttons are not available.
(Confirm) button to send the current
Figure 7.3
(Mode),
25
(Confirm) button to go to the
(Fan speed),
(Swing),