Ac/Dc Amps <600A Jaw - UEi DL599 Instruction Manual

Wireless trms clamp meter w/ 3-phase & unbalanced motor tests
Hide thumbs Also See for DL599:
Table of Contents

Advertisement

Find Quality Products Online at:
AC/DC Amps <600A Jaw
A U T O
A U T O
INRUSH
INRUSH
RANGE
RANGE
MIN/MAX
MIN/MAX
ZERO
ZERO
°C/°F
°C/°F
PEAK
PEAK
Hz / Duty
Hz / Duty
T r u e R M S
T r u e R M S
C L A M P M E T E R
C L A M P M E T E R
30V
30V
T
T
T
T
1
1
2
2
CATIV 600V
CATIV 600V
CATIII 1000V
CATIII 1000V
TEMP
TEMP
• Center wire in guides for best accuracy.
• Opposing currents cancel each other (use line-splitter when necessary).
• Keep hands below guard when measuring high current levels.
• Do not attempt to measure more than 600A AC / 600A DC.
Features:
SELECT
BT
AC Amps Measurement - Jaw input
Range
Resolution
Accuracy
60.00A
0.01A
±2.0% + 5dgts
600.0A
0.1A
±1.8% + 5dgts
45Hz to 400Hz True RMS
Minimum Current for Clamp Measurement: 0.3A
DC Amps Measurement - Jaw input
Range
Resolution
Accuracy
60.00A
0.01A
±2.0% + 5dgts
600.0A
0.1A
±1.8% + 5dgts
Minimum Current for Clamp Measurement: 0.2A
11
GlobalTestSupply
www.
Single
Conductor
Only
• Default = Auto Selection
• Press SELECT x1 =
• Press SELECT x2 =
Overload Protection
600V RMS
Overload Protection
600V RMS
.com
sales@GlobalTestSupply.com

Advertisement

Table of Contents
loading

This manual is also suitable for:

053533509137Dl589