Error Message and Trouble Shooting

6.3 Warning Codes (Field Warning)

Table 6-3A: Warning Codes (Field warning) & Messages
Message
DC Voltage
Low
Input voltage is under the limit
(W01)
1. Over temperature
2. Power Limit function
3. Power vs. Frequency function
4. P(V) function
De-rating
(W07)
5. Grid Voltage low
6. Solar Voltage low
7. Solar Voltage High
8. Ramp up function
1. DC Connectors polar is incorrect
String fault
2. String current monitoring function
(W08)
is failure

6.4 Warning Codes (Inverter Warning)

Table 6-4A: Warning Codes (inverter warning) & Messages
Message
1. One or more fans are locked
Fan Fail
2. One or more fans are defective
(W11)
3. One ore more fans are
disconnected
DC SPD Fault
1. One or more SPD are defective
(W17)
2. One or more SPD are
AC SPD Fault
disconnected
(W18)
Description
Description
Check the voltage connection to the
inverter terminal
1. Check the installation ambient and
environment
2. Check Grid Code & Grid setting
3. Check the utility frequency on the inverter
terminal
4. Check the utility voltage on the inverter
terminal
5-1. Check the utility voltage on the inverter
terminal
5-2. Check reactive power setting
6. Check the Solar voltage on the inverter
terminal
7. Check the Solar voltage on the inverter
terminal
8. Check Ramp up setting
1. Check the polarity of PV connection
2. Restart DC switch and AC breaker
3. Contact customer service for
technical support
Ext Fan Fail
1. Remove the object that stuck in the fan(s)
2. Check the connections of all fans
3. Replace the defective fan(s)
Int Fan Fail
Contact customer service for
technical support
1. Replace the defective SPD
2. Check the connections of SPDs
76
Action
Action