19 Configuration

19.1 Field setting

(1)
Field settings are defined as follows:
• M: Mode number – First number: for group of units – Number between brackets: for individual unit
• SW: Setting number / C1: First code number
• —: Value number / C2: Second code number
: Default
FXSN50~112A2VEB
CO₂ Conveni-Pack: indoor unit
4P602817-1 – 2020.02
Make the following field settings so that they correspond with the actual
installation setup and with the needs of the user:
Bottom suction or rear suction installation setting
External static pressure setting using:
-
Automatic airflow adjustment setting
-
User interface
Time to clean air filter
Function for refrigerant leak detection
To set bottom suction or rear suction installation
If you have an installation with...
Rear suction
Bottom suction
To set automatic airflow adjustment
The automatic airflow adjustment function measures the air volume and static
pressure and adjusts it towards the nominal air flow, whatever the length of duct.
When the air conditioning unit is running in fan operation mode:
1 Stop the air conditioning unit.
2 Set —/C2 to 03.
Setting content:
Airflow adjustment is OFF
Press ON/OFF to return to normal operating mode.
Possible consequence: The user interface operation
lamp will light up and the unit will start the fan
operation for automatic airflow adjustment.
Operation stops after 1 to 8 minutes.
Possible consequence: Setting is finished and the user
interface operation lamp will be off.
If there is no change after airflow adjustment, perform the setting again.
19
Configuration
|
(1)
Then
M
SW/C1
13(23)
11
Then
M
SW/C1 —/C2
11(21)
Installer and user reference guide
—/C2
01
02
(1)
7
01
03
02
69