To connect the drain piping to the indoor unit
FXSN50~112A2VEB
CO₂ Conveni-Pack: indoor unit
4P602817-1 – 2020.02
A
In case of rear suction installation 231 mm
In case of installation with canvas duct (field supply) 350~530 mm
a
Metal clamp (accessory)
b
Drain hose (accessory)
c
Rising drain piping (vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter) (field supply)
d
Hanging bars (field supply)
▪
Condensation. Take measures against condensation. Insulate the complete drain
piping in the building.
▪
Combining drain pipes. You can combine drain pipes. Make sure to use drain
pipes and T-joints with the correct gauge for the operating capacity of the units.
a
T-joint
NOTICE
Incorrect connection of the drain hose might cause leaks, and damage the
installation space and surroundings.
a
Drain outlet for maintenance
b
Refrigerant pipes
c
Drain pipe connection
1 Push the drain hose as far as possible over the drain pipe connection.
2 Tighten the metal clamp until the screw head is less than 4 mm from the
metal clamp part.
3 Check for water leaks (see
4 Wind the large sealing pad (= insulation) around the metal clamp and drain
hose, and fix it with tie wraps (accessory).
5 Connect the drain piping to the drain hose.