Daikin FXSN112A2VEB Installer And User Manual page 53

Co2 conveni-pack: indoor unit
Table of Contents

Advertisement

To connect the drain piping to the indoor unit
FXSN50~112A2VEB
CO₂ Conveni-Pack: indoor unit
4P602817-1 – 2020.02
A
In case of rear suction installation 231 mm
In case of installation with canvas duct (field supply) 350~530 mm
a
Metal clamp (accessory)
b
Drain hose (accessory)
c
Rising drain piping (vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter) (field supply)
d
Hanging bars (field supply)
Condensation. Take measures against condensation. Insulate the complete drain
piping in the building.
Combining drain pipes. You can combine drain pipes. Make sure to use drain
pipes and T-joints with the correct gauge for the operating capacity of the units.
a
T-joint
NOTICE
Incorrect connection of the drain hose might cause leaks, and damage the
installation space and surroundings.
a
Drain outlet for maintenance
b
Refrigerant pipes
c
Drain pipe connection
1 Push the drain hose as far as possible over the drain pipe connection.
2 Tighten the metal clamp until the screw head is less than 4  mm from the
metal clamp part.
3 Check for water leaks (see
4 Wind the large sealing pad (= insulation) around the metal clamp and drain
hose, and fix it with tie wraps (accessory).
5 Connect the drain piping to the drain hose.
1
1
a
b
a
Drain pipe connection (attached to the unit)
a
"To check for water
2~6
c
d
2
4
A A
A'
A'
A-A'
3
15
Unit installation
|
(mm)
4
leaks" [
 54]).
e
5
≤4 mm
d
c
b
a
Installer and user reference guide
53