  15‒1 Example graph for calculation
A
Refrigerant charge
B
Room volume
a
2 appropriate measures required
b
1 appropriate measure required
c
No measure required
For occupancies on the lowest underground floor of the building
If the total refrigerant charge (kg)
divided by the room volume
<RCL
>RCL and ≤QLMV
>QLMV and <QLAV
>QLAV
(a)
For occupied spaces with a floor area exceeding 250 m
determination of the room volume (Example: even if the room area is 300 m
room height is 2.5 m, calculate the room volume as 250 m
Example: Total refrigerant change in the system is 45  kg and room volume is
3
300 m
. 45/300 = 0.15, which is >RCL(0.072) and <QLAV(0.18), therefore install at
least 2 appropriate measures in the room.
70
65
a
60
55
50
45
40
35
30
25
20
15
10
5
0
0
50
100 150
200 250 300 350
  15‒2 Example graph for calculation
A
Refrigerant charge limit
B
Room volume
a
Installation is not allowed
b
2 appropriate measures required
c
1 appropriate measures required
d
No measure required
QLAV
b
400
450
500
550
600 650 700 750 800 850 900 950 1000
B (m³)
...the number of appropriate measures
(a)
3
(m
) is...
must be at least...
0
1
2
Value CANNOT be exceeded!
QLAV
b
400
450
500
550
600 650 700 750 800 850 900 950 1000
B (m³)
QLMV
c
2
2
, use 250 m
as the floor area for
2
and the
2
3
× 2.5 m = 625 m
)
QLMV
RCL
c
d
FXSN50~112A2VEB
CO₂ Conveni-Pack: indoor unit