Storage Temperature; Climate Class; Altitude According To Iec 61010-1 Ed.3; Degree Of Protection - Pepperl+Fuchs Pulscon LTC50 Technical Information

Guided level radar
Table of Contents

Advertisement

Pulscon LTC50
Operating conditions: Environment
8.3

Storage temperature

-40 ... +80 °C (-40 ... +176 °F)
8.4

Climate class

DIN EN 60068-2-38 (test Z/AD)
8.5

Altitude according to IEC 61010-1 Ed.3

Up to 2000 m (6600 ft) above MSL.
Can be expanded to 3000 m (9800 ft) above MSL by application of an overvoltage protection.
8.6

Degree of protection

• With closed housing tested according to:
• IP68, NEMA6P (24 h at 1.83 m under water surface)
• For plastic housing with transparent cover (display module): IP68 (24 h at 1.00 m
• IP66, NEMA4X
• With open housing: IP20, NEMA1
• Display module: IP22, NEMA2
Note!
Degree of protection IP68 NEMA6P applies for M12 PROFIBUS PA plugs only when the
PROFIBUS cable is plugged in and is also rated IP68 NEMA6P.
8.7

Vibration resistance

DIN EN 60068-2-64/IEC 68-2-64: 20 ... 2000 Hz, 1 (m/s
8.8

Cleaning the probe

Depending on the application, contamination or buildup can accumulate on the probe. A thin,
even layer only influences measurement slightly. Thick layers can dampen the signal and then
reduce the measuring range. Severe, uneven buildup, adhesion e. g. through crystallization,
can lead to incorrect measurement. In this case, we recommend that you use a non-contact
measuring principle, or check the probe regularly for soiling.
1
also valid for the "Sensor remote" version
2
This restriction is valid if the following options of the product structure have been selected at the same time: feature
"Display, Operation" = D "SD02" or E "SD03"; feature "Housing" = A1 (GT19).