When designing the photovoltaic system, ensure that all components are oper-
ated within their permitted operating ranges at all times.
Observe all the measures recommended by the solar module manufacturer to
ensure that the solar module retains its properties in the long term.
Obey the regulations of the power supply company regarding connection meth-
ods and energy fed into the grid.
Choice of loca-
tion
IP 66
NH
The inverter is suitable for indoor installation.
The inverter is suitable for outdoor installation.
Because of its IP 66 protection class, the inverter is resistant to
water jets from any direction and can also be used in damp en-
vironments.
In order to minimise the heating up of the inverter, do not ex-
pose it to direct insolation. The inverter should be installed in a
protected location, for example, e.g. in the area of the PV mod-
ules or under an overhanging roof.
U
at an altitude of:
DCmax
0 to 2000 m = 1000 V
2001 to 2500 m = 950 V
2501 to 3000 m = 900 V
3001 to 3400 m = 850 V
IMPORTANT! The inverter must not be installed or used at alti-
tudes above 3400 m.
Do not install the inverter in:
3
-
Areas where it may be exposed to ammonia, corrosive gases,
acids or salts
(e.g. fertiliser storage areas, vent openings for livestock
stables, chemical plants, tanneries, etc.)
During certain operating phases the inverter may produce a
slight noise. For this reason it should not be installed in an occu-
pied living area.
37