Fronius Symo Advanced 10.0-3-M Operating Instructions Manual page 115

Hide thumbs Also See for Symo Advanced 10.0-3-M:
Table of Contents

Advertisement

Fronius Symo Advanced
5)
Current (inrush)
Power factor (cos phi)
Maximum output fault current / duration
General data
Maximum efficiency
European efficiency U
DCmin
Self-consumption at night
Cooling
Protection class
Dimensions h x w x d
Weight
Permitted ambient temperature
Permissible humidity
EMC emission class
DC / AC overvoltage category
Pollution degree
Noise emission
Inverter topology
Protection devices
DC isolation measurement
DC overload performance
DC disconnector
RCMU
Active anti-islanding method
AFCI - Arc Fault Circuit Interrupter (Arc Guard)
AFPE (AFCI) classification (according to
IEC63027)
/ U
/ U
DCnom
DCmax
12.5-3-M
27.2 A peak /
5.18 A rms over 5.4 ms
2)
0–1 ind./cap.
64 A / 2.34 ms
97.8%
95.7 / 97.5 / 96.9%
0.7 W & 117 VA
Controlled forced-air
ventilation
IP 66
725 x 510 x 225 mm
34.8 kg
-25 °C - +60 °C
0-100%
B
2 / 3
2
65 dB(A) (ref. 1pW)
Non-insulated trans-
formerless
Integrated
Operating point shift,
power limiter
Integrated
Integrated
Frequency conversion
method
Integrated
F-I-AFPE-1-6-1
Full coverage
Integrated
AFPE
1 monitored string per in-
put port
6 input ports per channel
(AFPE for MPP1 & MPP2:
6)
1 monitored channel
4)
115

Advertisement

Table of Contents