After first power ON of the system, the user interface will guide you using the
configuration wizard. This way you can set the most important initial settings. This
way the unit will be able to run properly. Afterwards, more detailed settings can be
done via the menu structure if required.
To restart the configuration wizard, go to Installer
Configuration wizard [9.1].
Booster heater capacity
The capacity of the booster heater must be set for the power consumption control
feature to work properly. When measuring the resistance value of the booster
heater, you can set the exact heater capacity and this will lead to more accurate
energy data (e.g. for Power consumption control). The capacity of the booster
heater installed in the domestic hot water tank is 1,2 kW.
#
Code
[9.4.1]
[6-02]
Quick mode timer
#
Code
[9.4.3]
[8-03]
Description
Booster heater capacity [kW]. The
capacity of the booster heater at nominal
voltage.
Range: 0~10 kW
Description
Booster heater delay timer.
Start-up delay time for the booster heater when
heat pump domestic hot water mode is active
and tank operation mode is Quick, refer to
4
"10.6.2 Tank" [
 70].
When heat pump domestic hot water mode is
active and tank operation mode is Quick, the
delay time is 20  minutes by default. End user
can select 3 predefined values: 10, 20, or 30
minutes, see Operation mode, refer to
"Operation
mode
4
timer" [
 77].
The delay time starts from the moment the
heat pump begins domestic hot water
production.
By adapting the booster heater delay time
versus the maximum running time, you can find
an optimal balance between the energy
efficiency and the heat up time.
If the booster heater delay time is set too high,
it might take a long time before the domestic
hot water reaches its set temperature.
Range: 5~95 minutes. If Installer set values of
[8-03] other than the 3 preset values for end
user, it will be displayed in Tank > Quick mode
timer as "set by installer". We recommend to
select one of the preset values for end user.
10
Configuration
|
settings >
and
Quick
mode
Installer reference guide
83

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ekhwet120b v3 seriesEkhwet90b v3 series

Table of Contents