Setup And Configuration - Dhw Tank; Setting Up The Power Consumption Control - Daikin EKHWET-BV3 Installer's Reference Manual

Domestic hot water tank
Hide thumbs Also See for EKHWET-BV3:
Table of Contents

Advertisement

6.2.3 Setup and configuration – DHW tank

6.3 Setting up the power consumption control

EKHWET90+120B
R32 Split series – Domestic hot water tank
4P680077-1A – 2022.11
Possible DHW tank volumes
Type
Standalone DHW tank
Energy saving tips
If the DHW consumption differs from day to day, you can program a weekly
schedule with different desired DHW tank temperatures for each day.
The lower the desired DHW tank temperature, the more cost effective. By
selecting a larger DHW tank, you can lower the desired DHW tank temperature.
The heat  pump itself can produce domestic hot water of maximum 53°C (or
lower according to outdoor temperature). The electrical resistance integrated in
the tank can increase this temperature. However, this consumes more energy.
We recommend to set the desired DHW tank temperature below 53°C to
minimize using the electrical resistance.
In case multiple indoor units are connected to the outdoor unit: when the
heat pump produces domestic hot water (DHW), depending on total demand for
Air Conditioning (A/C) and the scheduled priority setting, it might not be able to
do both DHW and A/C at the same time. In case you need DHW and A/C at the
same, we recommend to produce the domestic hot water during the night when
there is lower A/C demand or during the time when occupants are not present.
For large DHW consumptions, you can heat up the DHW tank several times
during the day.
To heat up the DHW tank to the desired DHW tank temperature, you can use the
following energy sources:
-
Thermodynamic cycle of the heat pump
-
Electrical booster heater
For more information about:
-
Optimising the energy consumption for producing domestic hot water, see
4
"10 Configuration" [
-
Connecting the water piping of the standalone DHW tank to the indoor unit,
see the installation manual of the DHW tank.
You can use the following power consumption controls. For more information
about the corresponding settings, see
#
1
"6.3.1 Permanent power
Allows you to limit the power consumption of the entire heat pump
system (sum of outdoor unit, indoor unit and booster heater) with one
permanent setting.
Limitation of power in kW or current in A.
90 l
120 l
 51].
"Power consumption
Power consumption control
limitation" [
4
 26]
6
Application guidelines
|
Possible volumes
4
control" [
 85].
Installer reference guide
25

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ekhwet120b v3 seriesEkhwet90b v3 series

Table of Contents