7.1.3 Installation patterns
Depending on the type of room in which you install the indoor unit, different installation patterns are allowed:
Room type
Living room, kitchen, garage, attic, basement, storage
room
Technical room (i.e. room that is NEVER occupied by
persons)
Ventilation openings
Minimum floor area
Restrictions
EKHWET90+120B
R32 Split series – Domestic hot water tank
4P680077-1A – 2022.11
PATTERN 1
A
1a
N/A
Room A
4
See
"PATTERN
1" [
32],
"Tables for PATTERN 1 and
A
Room A (= room where indoor unit is installed)
B
Room B (= adjacent room)
c1
Bottom opening for natural ventilation
c2
Top opening for natural ventilation
H
Actual release height:
release
From floor to 100 mm below top of the unit.
N/A
Not applicable
Minimum floor area / Release height:
▪
The minimum floor area requirements depend on the release height of the
refrigerant in case of a leakage. The higher the release height, the lower the
minimum floor area requirements.
▪
The default point of release is 100 mm below the top of the unit.
▪
You can also take advantage of the floor area of the adjacent room (= room B) by
providing ventilation openings between the two rooms.
▪
For installations in technical rooms (i.e. room that is NEVER occupied by
persons), additionally to patterns 1 and 2, you can also use PATTERN 3. For this
pattern there are no requirements to the minimum floor area if you provide 2
openings (one at the bottom, one at the top) between the room and the outside
to ensure natural ventilation. The room must be protected from frost.
Allowed patterns
PATTERN 2
A
B
c2
2a
c1
Between room A and B
Room A + Room B
4
"PATTERN
2" [
32], and
2" [
4
33]
7
Unit installation
|
1, 2
1, 2, 3
PATTERN 3
A
c2
c1
Between room A and
outside
N/A
See
"PATTERN
3" [
Installer reference guide
4
35]
31