5.3

Configuring the Fault Text

VAR4/12/20 Menu: Configuration System Router Control Contacts <Contact #
VAR8/VAR8-ACU Menu: Configuration System Router Ctrl Contacts <Digital #
Possible values:
System default configuration: 'EXT FAULT' (VAR4/12/20)
For EN 54-16, ISO 7240-16 and BS 5839-8 compliance, modify the fault text to 'BATT BACKUP FAULT'
or other text that identifies the fault as reported by the battery backup system.
5.4

Configuring the Fault Type

VAR4/12/20 Menu: Configuration System Router Control Contacts <Contact #
VAR8/VAR8-ACU Menu: Configuration System Router Ctrl Contacts <Digital #
Possible values:
System default configuration: 'EN54 Power Fault=No'
The EN 54 Power Fault when set to 'Yes' enables the Router to indicate 'POWER' fault on the bottom line of
the LCD display when the contact reports a fault.
For EN 54-16, ISO 7240-16 and BS 5839-8 compliance, set the fault type to 'EN54 Power Fault=Yes'.
BPC130 / BDIST / MDIST – Product Manual
'EXT FAULT'
'CONTACT FAULT' (VAR8/VAR8-ACU)
External Fault EN54 Power Fault EN54 Power Fault=Yes
External Fault EN54 Power Fault EN54 Power Fault=Yes
'EN54 Power Fault=No'
'EN54 Power Fault=Yes'
U-0456-0145.doc – Issue: 04 complete, approved
Page 24 of 40
nn
>
External Fault Description
nn
>
External Fault Desc.
nn
>
nn
>