ABB ARC600 User Manual page 76

Wireless controller
Hide thumbs Also See for ARC600:
Table of Contents

Advertisement

Technical data
Description
Table 38: I/O specifications
Description
Digital inputs
Digital outputs
Table 39: Network interfaces
Description
Ethernet ports
Serial ports
Table continues on the next page
76
Extra reserved for other use
Total number of analog in-
puts
1
Number of digital inputs
Operating range
Current drain
Power consumption/ input
Input polarity
Isolation
Number of digital outputs
Output pin rated voltage
Continuous carry 30 VDC
Ethernet/LAN
Serial 1/Console
1MRS758459 J
Value
1
2
Value
17
18...60 V DC (>18 V DC detec-
ted as 1)
3.5...12.5 mA
<0.8 W
bipolar
3 kV
10
24 VDC
1 A
Value
10/100 Base-T. Shielded RJ-45
1.5 kV isolation transformer
Ethernet IEEE 802-3, 802-2
RS-232 DTE
Male DB-9 connector
IEC 60870-5-101 protocol sup-
port
Full serial and modem signals
300...460 800 bps
Data bits: 7 or 8
Stop bits: 1 or 2
Parity: None, Even, Odd
ARC600
User Manual

Advertisement

Table of Contents
loading