IEC-104 application settings
Name
Use packet collector
Max bytes
Max time
Max packets
Other settings
Write syslog
66
Description
rately. This function is useful for slow packet
switched communication network (for example
Mobitex) for speeding up especially the general
interrogation response.
Determines if the packet collector is in use.
Max bytes defines the maximum bytes trigger
for packet collector. Before a new packet is inser-
ted into the packet collector buffer the amount
of bytes is checked. If the insertion of the new
packet would cause the number of bytes in the
packet collector to exceed MAX BYTES, the old
content is sent to the network before inserting
the new one. The value should be smaller than
the MTU/MRU of network used.
Max time defines the maximum collect time trig-
ger for packet collector in 0.1 second increments
for packet collector. If there has been data on
packet collector over MAX TIME, the data is sent
to network. The value must be smaller than t1.
Max packets defines the maximum amount of
IEC-101 packets stored into the packet collector
before sending the data to the network.
Write syslog defines if the error messages are
stored to system log file or not. The system log
is available by using Web user interface.
1MRS758459 J
Value range
No, Yes
1...1500
1...255
1...255
No, Yes