ABB ARC600 User Manual page 75

Wireless controller
Hide thumbs Also See for ARC600:
Table of Contents

Advertisement

1MRS758459 J
Table 37: Default I/O configuration
Description
Digital inputs (0...60 V DC,
>18 V DC detected as 1)
Digital outputs (1 A/30 V DC
continuous carry)
Analog inputs (-5...+5 V
measurement, ±300 mV for
-10...+55°C, 0 V...+5 V)
Table continues on the next page
1
Digital inputs are designed for reading the status of the feeder (open, traveling, closed) and not
for detecting short-duration changes.
ARC600
User Manual
Digital inputs for the discon-
1
nector status control
Disconnector 1: Open/
closed, local/remote use,
grounding open/closed –
5 pcs
Disconnector 2: Open/
closed, local/remote use,
grounding open/closed –
5 pcs
Disconnector 3: Open/
closed, local/remote use,
grounding open/closed –
5 pcs
Extra general purpose digital
inputs reserved for other use
Total number of digital inputs 17
Digital outputs for the dis-
connector open/close com-
mand
Disconnector 1: Open/
close – 2 pcs
Disconnector 2: Open/
close – 2 pcs
Disconnector 3: Open/
close – 2 pcs
Digital output for the load cut
(motor overload protection)
Digital output for the test
load of the battery test (test
load)
Digital output for the external
heater
Extra general purpose digital
output reserved for other use
Total number of digital out-
puts
Load measurement (DC mo-
tor load current)
Technical data
Value
15
2
6
1
1
1
1
10
1
75

Advertisement

Table of Contents
loading

Table of Contents