1MRS758459 J
Description
Casing
Approvals
Environmental conditions
Table 32: Battery recommendations
Description
Rated voltage
Capacity
Weight
Size (L × W × H)
Table 33: Supply for external devices and input circuits (X2.1 pin 6)
Description
Output voltage
Output current
Output overvoltage protection level
1
The maximum operating temperature is +40°C at 1 A load on X2.1 pin 6.
ARC600
User Manual
Inrush current 25°C, 230 V AC
Input fuse
Power consumption
Overvoltage transient protec-
tion
Holdup time (230 V, 100%
load)
1
Temperature range
Relative humidity
Yasa NP 17-12
12 V
17 Ah
6.1 kg
181 × 76 × 167 mm
Value
21...29 V
1 A continuous, 2.2 A peak
30.5 V
Technical data
Value
Output 3000 V AC RMS 50 Hz
1 min
Output/ground 500 V DC
<25 A <5 ms
T3.15 A high breaking
10 W typical (when not charg-
ing battery), 60 W (full charg-
ing)
VDR 275 V AC 72 J
>50 ms
Aluminium shell
CE
-30...+55°C (non condensing)
-40...+70°C (storage)
5...85% RH
Yasa NPL 24-12
12 V
24 Ah
9 kg
166 × 175 × 125 mm
73