IEC-104 application settings
Name
Max sequence number
Flush buffered events
on connection
Cause of transmission
length
Common address
length
Info object address
length
IEC-101 settings
Slave link address
Link address field
length
Event poll interval
Link test interval
Keep link open
Table continues on the next page
64
Description
bility of detecting partially closed network con-
nections especially in UDP mode.
These are the maximum sequence number used
in IEC-104 communication. The default value "0"
equals to 32767 as suggested by the IEC-104
standard.
Defines if buffered events are flushed on new a
IEC-104 connection.
It defines the length of IEC-104 Cause of trans-
mission ASDU header field in bytes. The IEC-104
standard defines value "2".
This defines the length of IEC-104 Common ad-
dress ASDU header field in bytes. The IEC-104
standard defines value "2".
This defines the length of IEC-104 Information
object address ASDU header field in bytes.
The IEC-101 settings define the properties of
IEC-101 link layer and application layer parame-
ters as described in the IEC 60870-5-101 stand-
ard. The IEC-101 communication is carried out
between the device and a IEC-101.
The link-level address of IEC-101 slave.
Defines the length of the IEC-101 link-level ad-
dress field in bytes. The link-level address of
IEC-101 slave.
Event poll interval defines the IEC-101 event poll-
ing interval in 0.1 second increments (class 1
or 2 poll). The events are polled only when the
IEC-104 connection is active.
Link test interval defines the IEC-101 link test in-
terval in 0.1 second increments. Link test is per-
formed if there is no other activity. The link test
is performed if there is no other activity during
defined interval.
Defines that the IEC-101 link is kept always open
even when there is no active IEC-104 connection.
If the functionality is enabled the device sends
link test frames and restarts the
IEC-101 link if the test fails. The events are still
not polled before the IEC-104 connection is ac-
tive. Some IEC-101 slaves require the link to be
continuously open in order to operate.
1MRS758459 J
Value range
0...32767
No, Yes
1, 2, 3
1, 2, 3
1, 2, 3
1...65000
1, 2
1...65000
1...65000
No, Yes
ARC600
User Manual