ABB ARC600 User Manual page 65

Wireless controller
Hide thumbs Also See for ARC600:
Table of Contents

Advertisement

1MRS758459 J
Name
Reply header timeout
Reply end timeout
Retry limit
Cause of transmission
length
Common address
length
Info object address
length
ASDU Converter
Use ASDU converter
Use ASDU type replacer
IEC-101
ASDU type
IEC-104
ASDU type
Convert short IEC-101
time stamps
Packet collector
Table continues on the next page
ARC600
User Manual
Description
Defines the timeout in milliseconds that the de-
vice waits the reply to start from IEC-101 slave
after command or request.
Defines the maximum duration of IEC-101 slave
response in seconds.
Defines the number of retries sent to a IEC-101
slave in case of no reply. If no reply is still re-
ceived the device closes the IEC-101 and IEC-104
connections.
Defines the length of IEC-101 cause of transmis-
sion ASDU header field in bytes. The IEC-101
standard defines value 1.
Defines the length of the IEC-101 common ad-
dress ASDU header field in bytes. The IEC-101
standard defines value 2.
Defines the length of IEC-101 information object
address ASDU header field in bytes. The IEC-101
standard defines value 2.
The ASDU converter can be used to convert AS-
DU header field lengths between IEC-101 and
IEC-104 protocols.
This defines if the ASDU header level conversion
between IEC-101 and IEC-104 is performed. If en-
abled the ASDU header field lengths are conver-
ted between IEC-104 and IEC-101. This parame-
ter must be enabled if the ASDU header lengths
differ between the IEC-104 and the IEC-101. The
information on the field must fit in the shorter
one of the two. It's not possible to convert e.g.
value 12000 to a one byte field.
The ASDU type replace function can be used to
convert an ASDU type (Original type) to anoth-
er (Applied type) type e.g. in cases when the
IEC implementation differs between master and
slaves.
The original ASDU type searched by ASDU type
replacer.
The new ASDU type is replaced by the original
type.
Defines if 56-bit timestamps are converted to
24-bit.
The packet collector can be used to collect many
IEC-101 messages and events to a single network
packet instead of sending every message sepa-
IEC-104 application settings
Value range
1...65000
1...65000
0...65000
1, 2, 3
1, 2, 3
1, 2, 3
No, Yes
No, Yes
0...255
0...255
No, Yes
65