Fig. 18 Application Example - Current Measurement At A Motor - Beckhoff KS3403 Installation Manual

3-phase power measurement terminals
Table of Contents

Advertisement

Polarity of the current transformers
If negative power values are measured on a circuit, please check whether the associated current
transformer circuit is connected correctly.
Current measurement on a motor
Make sure terminal point N is zeroed or grounded!
If you do not connect the terminal point N with the neutral conductor of your mains supply (e.g. if the
KL3403 is used purely for current measurements), terminal point N should be earthed, in order to avoid
dangerous overvoltages in the event of a current transformer fault!
Fig. 18: Application example - current measurement at a motor
KL3403/KS3403
CAUTION
Version: 3.2.0
Mounting and wiring
29