Operating Specifications; Installation Procedure - Pentair EVERPURE ENDURANCE EV943730 Installation, Operation, Maintenance Manual

High-flow filtration systems
Table of Contents

Advertisement

MOUNTING & CONNECTION CONSIDERATIONS
The location selected for system installation should allow for:
• Adequate space for "in" and "out" water line connections.
• Mounting screws should anchor into a solid structure.
• The frame is designed to mount on 16" centers (wall studs).
• Allow five (5) inches below the cartridges for removal.
• The pretreatment housing can be removed from the frame and
mounted separately. Be certain to use adequate lengths of
opaque 3/4" beverage tubing.

OPERATING SPECIFICATIONS

• Temperature Limits: 35-100°F (2-38°C)
• Pressure Limits: 10-100 psi (0.689-6.9 bar)
• For cold water use only.
• Rated Service Flow:
Endurance® High Flow Twin system - 7.5 gpm (28.4 lpm)
Endurance High Flow Triple system - 11.25 gpm (42.6 lpm)
Endurance High Flow Quad system - 15 gpm (56.8 lpm)
DIMENSIONS
21.7"
(55.1cm)

INSTALLATION PROCEDURE

NOTE: For installations in Australia and New Zealand, product must
be installed with a backflow prevention device in accordance with
AS/NZS 3500 and AS/NZS 2845.1.
1. The predrilled mounting holes in the bracket can be used as a
guide. The holes are on 16" centers. Mark and insert anchors or
screws in the wall.
NOTE:The large pretreatment cartridge can be removed from
the bracket and mounted separately.
2. Follow steps 3-6 only if the pretreatment cartridge (Pleated
Endurance HF) is going to be mounted separately. Otherwise,
proceed to Step 7.
3. Disconnect the hose between the pretreatment head and the
manifold.
4. Unscrew the two screws that hold the pretreatment bracket to
the main bracket.
2 • PENTAIR® EVERPURE® ENDURANCE HIGH-FLOW WATER FILTRATION SYSTEMS INSTALLATION, OPERATION & MAINTENANCE GUIDE
• Give consideration to the weight of the system when filled with
water. Operating weights of the Everpure Endurance High‑Flow
systems are:
• Endurance High‑Flow Twin - 58.4 lbs. (26.5 kg)
• Endurance High‑Flow Triple - 63.8 lbs. (28.9 kg)
• Endurance High‑Flow Quad - 69.1 lbs. (31.3 kg)
• Service Life Between Cartridge Changes:
Endurance High Flow Twin system -
100,000 gal (378,541 liters) or 1 year
Endurance High Flow Triple system -
150,000 gal (567,812 liters) or 1 year
Endurance High Flow Quad system -
200,000 gal (757,082 liters) or 1 year
26"
(66 cm)
Remove Screws
33.2"
(84.3 cm)
18.7"
(47.4 cm)
Figure 1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Everpure endurance ev943731Everpure endurance ev943732