Book Mount Procedure - Omron Sysmac NY Series Hardware User Manual

Hide thumbs Also See for Sysmac NY Series:
Table of Contents

Advertisement

5 Installation
5-3-8

Book Mount Procedure

Use the following procedure to mount the IPC RTOS Controller in the book orientation.
Additional Information
• Refer to 5-4-2 Ground on page 5-29 for grounding details.
• Refer to 2-9-1 Mounting Brackets on page 2-17 for the bracket model.
To mount the Box PC:
1
Mount the Bracket A to the Industrial Box PC C with the 6 Phillips screws B supplied with
the brackets. Tighten these screws with a torque of 0.5 N·m.
2
Mount the Box PC with the bracket in position.
• Drill the four holes at the location where the Box PC with bracket will be mounted.
Refer to 4-1-8 Bracket Specifications on page 4-9 for details.
• Position the Industrial Box PC with bracket in the mounting location.
5-26
A
B
C
NY-series IPC RTOS Controller Hardware User's Manual (W581)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac nyb1c-31a81Sysmac nyb1c-31a91Sysmac nyb1c-31ac1Sysmac nyb1c-31ak1Sysmac nyb1c-31b81Sysmac nyb1c-31b91 ... Show all