Forced Air Circulation
Room Cooling
Cool the entire room where the control panel is located.
Low Temperatures
The Box PC may not start normally if the temperature is below 0°C when the power is turned ON.
Maintain an air temperature of at least 5°C inside the panel, by implementing measures such as instal-
ling a low-capacity space heater in the panel.
Alternatively, leave the Box PC power ON to keep the Box PC warm.
5-3-4
Humidity
Rapid temperature changes can cause condensation to occur, resulting in malfunctioning due to short-
circuiting.
When there is a possibility of this occurring, take measures against condensation, such as leaving the
Box PC power ON at night or installing a heater in the control panel to keep it warmer.