Connector Cna Base Board"N2Ba; Dip Switch Programming; Dip Switch Sw1 Frontal Board "N2Fr - Notifier MINIGAS Installation And Programming Manual

Table of Contents

Advertisement

19
RL Sounder LC + Reset
20
RL Sounder LC - Reset
21
OC ZONE 1 Pre-alarm
22
OC ZONE 1 Alarm
23
OC ZONE 2 Pre-alarm
24
OC ZONE 2 Alarm
25
POSITIVE 24 V USER
26
NEGATIVE 24 V USER
12.2 Connector CNA base board "N2BA"
NO.
DENOMINATION
TERM.
1.
L1
2.
PE
3.
L2
13 – DIP SWITCH PROGRAMMING

13.1 Dip switch SW1 frontal board "N2FR"

In TRACKING mode the pre-alarm and alarm output relays and the pre-alarm and alarm relays check in
real time the zone pre-alarm and alarm status.
In no TRACKING mode the pre-alarm or alarm time remain active for the setted time even if the line has
been restored to the regular status.
PRE-ALARM activation time
TRACKING mode
1 minute
5 minutes
15 minutes
ALARM activation time
Infinite
3 minutes
10 minutes
15 minutes
OPEN COLLECTOR output mode
NORMAL
TRACKING mode
In NORMAL mode the OPEN COLLECTOR output and the relative led zone memorize the events; in
TRACKING they follow the events recording in real time.
MINIGAS 2001
3_Minigas2001-install-eng
MAX
End of line resistor
1A
Supervisory current < 1,2 mA
30 mA – 24 Vcc
30 mA – 24 Vcc
30 mA – 24 Vcc
30 mA – 24 Vcc
0.8A
NOTES
CONTROL PANEL
Fase
Heart
Neutre
Installation and Programming Manual
Doc. M-011.1-MGAS-ENG Rev. A.1
= 2k7
SW1-1
OFF
ON
OFF
ON
SW1-3
OFF
ON
OFF
ON
SW1-5
OFF
ON
COLOR-
NO./CABLE
SW1-2
OFF
OFF
ON
ON
SW1-4
OFF
OFF
ON
ON
Pag. 17