9.

Handing over of the installation

Make repeated start attempts to ensure that the adjustments
function.
Close the ball valve during operation to check that the gas switch
switches off at the set value.
Remove the hose for the air pressure switch to check that the burner
locks out.
Check that all protective covers and measurement nipples are
mounted and fastened.
Fill out necessary test reports.
Instruct the persons in charge of the operation on the service and
maintenance of the installation and what to do should any troubles
occur.
Inspection and service must be carried out by authorized personnel.
!
Review and service should be performed by authorised
personnel only.