Function Lme - Bentone BG 550 M LN Installation And Maintenance Instruction

Table of Contents

Advertisement

3.2.1
Components
A1
Burner control
A2
Power control
B1
Ionization electrode
F1
Operating fuse
F2
Operation fuse
F3
Operation fuse
H1
Operating lamp
K1
Contactor + Overload protection
M1
Motor
M2
Damper motor
Q1
Signal amplifier AGQ (accessory)
R1
UV-detector (accessory)
3.3

Function LME

1.
Operating switch ON-Thermostat ON-Gas pressure switch ON-Air
damper closed.
Check that the air pressure switch does not indicate fan pressure,
then the motor starts.
2.
Damper motor opens.
The damper motor opens the damper to the maximum load position.
Check that the air pressure switch indicates sufficient fan pressure.
3.
Damper motor closes.
The damper motor closes to the minimum load position, then the
ignition spark is produced.
4.
Main and safety valves open.
The gas ignites and the ionisation electrode indicates flame.
5.
The safety time ends.
Ignition spark and safety time cease. If the spark is missing or it
disappears after this time limit, the gas burner control is blocked.
6.
Operating position.
The burner is in operating mode and can now switch to the capacity
controlled by the controller.
7.
Stop.
The burner operation can be stopped with the operating switch or the
thermostat.
If the gas burner control is blocked
The red light in the gas burner control comes on. The burner is restarted by
pressing the reset button.
3.2.2
Technical data
Preiginition time
Prepurge time
Postignition time
Safety lockout time
Reset time after lockout
Reaction time on fl ame failure
Min. ionisation current at fl ame
Max. ionisation current
12
Bentone
S1
Operating switch
S3
Control thermostat
S4
Temperature limiter
S5
Safety switch for hinged door
S7
Main switch
S8
Air pressure switch
S9
Gas pressure switch, min
S11
Change-over switch, Man-Auto
S12
Change-over switch, Increase-
Decrease
S15
Control thermostat, 3-pole (only
for 2-stage sliding)
S20
Main switch 1-phase
LME22.232C2E
3 s
20 s
2.5 s
< 3 s
< 1 s
< 1 s
5 µA
20 µA
T1
Ignition transformer
X1
Connection terminal board
X2
Earth terminal
X3
Plug-in contact, burner
X4
Plug-in contact, boiler
X7
Plug-in contact, 3-phase, burner
X8
Plug-in contact, 3-phase, boiler
X15
Plug-in contact, power
controller, burner
X16
Plug-in contact, power controller
Y1
Solenoid valve 1
Y3
Solenoid valve 3
Mains connection and
!
fuse in accordance with
local regulations.