Control Of Flame Monitoring And Ionization Current - Bentone BG 550 M LN Installation And Maintenance Instruction

Table of Contents

Advertisement

Control of flame monitoring and ionization
8.8
current
The burner is monitored in the standard version according to the ionization
principle. The ionization current must be checked at each service occasion.
The ionization current is measured with a microampermeter (µA) which is
connected in series with the flame electrode and the gas burner control.
Connect the µA meter as shown below. The minimum required ionization
current is shown in the table. During normal operation, this current must be
significantly higher, preferably more than 10 µA.
The reason for too low ionization current can be creep current, poor connection
to earth, dirt or that the flame electrode may need to be adjusted. The wrong
gas/air mix can also cause too low ionization current.
Technical data
Idle voltage at ION-terminals
Short-circuit current
Min. current for flame detection
Required current to ensure detection
Possible detection current
Operational indicator lamp flashes green
Operational indicator lamp shines green
8.8.1
Flame monitoring ionisation
34
Bentone
AC 115-230V
Max. AC 100-300 mA
Min. DC 1.5 µA
Min. DC 3 µA
Max. DC 20 µA
<5 µA DC
>5 µA DC
172 615 02-3