Page 1
178 096 82-3 P93783 2023-06-27 Providing sustainable energy solutions worldwide Installation- and maintenance instruction BG 650i M J/K LMV37 MB-DLE 415 IP54 Translation of the original instructions.
Page 2
1~230V 1,0A 50Hz IP 20 Motor supply MADE IN SWEDEN BY 1. Manualer på övriga språk 1. Manuals in other languages 1. Manualer på andre sprog 2. www.bentone.com\ 2. www.bentone.com\download 2. www.bentone.com\ nedladdning eller scanna or scan QR-code. download eller scan QR-koden.
Make sure that the burner is suitable for the application (see Technical • Data). All components must be installed without being bent, twisted or • subjected to mechanical or thermal forces that affect components. 172 515 01-2 2021-10-05 Bentone...
Prevent open flames or sparking, e.g. do not turn lights on or off, do • not use any electrical appliances or mobile phones. • Evacuate the building. Notify the installer or gas supplier of the problem so that it can be • rectified. Bentone...
*743 *343 **200 * The above dimensions are max. measurements. Depending on the components used, the measurements may vary. ** Min. recommended distance to floor. 2.1.1 Measurements for connection to the boiler (ø210) ø255-290 Ø (170)190 172 515 95-3 2023-04-04 Bentone...
Installation must be done so it does not prevent air supply to the burner. Working field G20, G25 - 200-1125 kW mbar G30, G31 - 200-1125 kW Do not exceed working field. 1000 1100 1200 Bentone...
Page 10
Damper motor, air Air pressure switch Transformer Brake plate Ignition electrode Ionization electrode Nozzle 2.6.1 Components – Electrical cabinet (Automatic control unit) AZL display for LMV Automatic control unit Switch 0-I Main switch Automatic control unit LMV Contactor Overload protection Fuse Bentone...
Air pressure switch LMV Automatic control unit Pos. 5b, 7: Components not required according to EN 676. Required over 1200 kW according to EN 676. This burner must not be used for biogas without first contacting Enertech. 172 515 86 2018-08-02 Bentone...
Contactor + Overload protection Connection terminal board Motor Connection, Damper motor - Air Operation switch Connection, Damper motor - Gas Main switch Connection, Display Air pressure switch Solenoid valve 1 Gas pressure switch, min Solenoid valve 2 172 615 60-2 Bentone...
Example: Modulating gas burner The system components (display and operating unit, actuators) are connected directly to the LMV37.4... basic unit. All safety-related digital inputs and outputs of the system are monitored by a contact feedback network. 172 525 67-2 Bentone...
6.3 AT (DIN EN 60127 2 / 5) Mains supply: Input current depending on the operating state of the unit Under voltage Safety shutdown from operating position at mains voltage LMV37.400A2 Approx. AC 186 V Restart on rise in mains voltage LMV37.400A2 Approx. AC 195 V Bentone...
Page 16
X5-02 pin 2/3 RAST plug Function / Outputs pin number X3-05 pin 1 X4-02 pin 2/3 X6-03 pin 2/3 X8-02 pin 1/3 X7-01 pin 2/3 X7-02 pin 2/3 X3-05 pin 2 0° 0° 0° Legend to the sequence diagrams Bentone...
Page 17
Postpurge time (t3) Evacuation of test space Atmospheric pressure test Filling of test space Gas pressure test Gas shortage waiting time Valve proving is performed depending on the parameter settings: Simultaneously with the prepurge time and/or the afterburn time. Bentone...
Page 18
Only with fuel train Lo and 2 fuel valves Parameter 223: Repetition limit value gas pressure switch-min in connection with gas shortage program parameter 246 (phase 90) Max. drop-in/response time for air pressure switch Alternative to valve proving Alternative to pressure switch-max (Pmax) or POC Bentone...
Page 19
0°/10% Position as supplied (0°) 90°/100% Actuator fully open (90°) Input/output signal 1 (ON) Input/output signal 0 (OFF) Input permissible signal 1 (ON) or 0 (OFF) Bentone...
Protection earth (PE) Supply for fuel meter Input fuel meter Shielding: For shielding the cables on the VSD, refer to: Siemens SED2 VSD Commissioning Manual (G5192), chapters 4 and 7, or • Danfoss Operation Manual VLT 6000 (MG60A703), chapter Installation • Bentone...
Page 21
Speed feedback signal Speed feedback signal Signal reference PWM speed output PWM speed output Signal reference DC 24 V external DC 24V external Controller input 4...20 mA Controller input 4...20 mA Power source Power source Analog Analog Controller Controller Bentone...
- For changing to a higher menu level (press button for 3…8 s) - For changing the operating mode (press button for >8 s) Enter in parameter setting mode • /reset • Reset in the event of fault • One menu level down Bentone...
Page 23
Figure 4: Meaning of display Fault status message Flame present Valve controlled Ignition controlled Fan motor controlled Oil preheater on Heat request from controllers Parameter setting mode Info mode Service mode h min s Actuator closing Actuator opening Unit of current display Bentone...
Postpurge time (t3) (abortion when load controller ON) Ph80 Valve proving test evacuation time Ph81 Valve proving test time atmospheric pressure, atmospheric test Valve proving filling test, filling Ph82 Ph83 Valve proving time gas pressure, pressure test Ph90 Gas shortage waiting time Bentone...
Change to normal Change to normal display display >3 s <8 s Info level /reset >3 s <8 s /reset or automatic return after timeout of menu operation Service level (parameter 127) >8 s >1 s Parameter level Parameter level Bentone...
Page 26
Basic unit Air-fuel ratio control curves (primary setting) /reset Bild 388e/1109 /reset Air-fuel ratio control /reset The following sections explain the Actuator operating philosophy behind the parameter levels using a number of examples. /reset Error histery /reset Process data Bentone...
Page 27
Standardized speed Number of faults Error history: 701-725.01.Code 701. chronological error list index value of index Indexlista: 01 = error code 02 = diagnostic code 03 = error class 04 = error phase 05 = startup counter 06 = output Bentone...
Page 28
The next bar starts flashing. h min s Complete the rest of the password according to the principle described. Example: Password consisting of 4 characters. min s After entery of the last character the password must be confirmed by pressing /reset Bentone...
400 for initial commissioning and for setting air-fuel controll. Press /reset 201: appears flashing. h min s Press to go to the settings for air-fuel ratio control and parameter 201 for selecting the operating mode. Bentone...
Page 30
20 = gas modulating with pilot only when firing on gas (Gp1 mod fuel active) • 21 = gas modulating with pilot only when firing on gas (Gp2 mod fuel active) • 22 = oil modulating only when firing on oil (Lo mod fuel active) • Bentone...
Page 31
Select your setting by pressing one of the buttons to save the setting for parameter 542: VSD Press This manual describes “0=VSD OFF” type burners. /reset Press: to return to parameter level. To the next parameter . Back to the previous parameter Bentone...
Page 32
P0 of the fuel damper. Press simultaneously Set a suitable fuel-air mixture so that the burner starts. Example: 30.0 h min s to set ignition position P0 of the air actuator. Press simultaneously Bentone...
Page 33
To the next curvepoint P9 appears flashing. Curvepoint for high-fire. Same procedure as with P0 h min s Note: is pressed first, the display jumps to 90! Back to the previous curvepoint When curvepoint 9 is set, press to start the burner. Bentone...
Page 34
This method makes the setting work easier and faster to complete. A more “correct” setting is obtained straight away. The process may need to be redone if the wrong input power was set for P9 initially. For this reason, be extremely careful when entering the first setting of P9. Bentone...
Page 35
Phase Fan ramp up (fan motor = ON, safety valve = ON) h min s Phase Traveling to prepurge position h min s Phase Prepurging h min s Phase Traveling to ignition position h min s Bentone...
Page 36
Phase Traveling to ignition position h min s Phase Preignition h min s Phase for first safety time (ignition transformer ON) h min s Phase for first safety time (ignition transformer OFF), preignition time OFF h min s Phase Interval 1 min s Bentone...
Page 37
Move along to curvepoint (high-fire point) P9; allow the burner to reach high-fire point P9. When P9 flashes, press If the burner goes into blocking mode when increasing to full load, restart the setting procedure and adjust the curvepoints in order to avoid the burner entering blocking mode. Bentone...
Page 38
The setting curve is therefore adjusted to the highest input power that the installation can handle. The desired input power is then set by entering how much of the maximum power is required. Bentone...
Page 39
When symbol or is no longer highlighted, you can press ESC a second time. h min s to exit parameter level. Press h min s The settings for air-fuel ratio control by the LMV37.4... are now completed. Bentone...
Page 40
0 = QRB / QRC 1 = ION / QRA Factory settings marked with bold text. When replacing detector flame between ionisation and UV-cell (QRA), no change to the setting parameters is required; simply disconnect and connect ionisation and UV-cell (QRA) respectively.. Bentone...
Page 41
When the Purging in the lockout position function is used, the fan may only be powered via a contactor and must not be connected directly to LMV37.4 (X3-05 pin 1)! Bentone...
Page 42
23 hours and 45 min of uninterrupted operation, followed by an automatic restart. When forced intermittent operation is inactivated the burner will run continuously. Forced intermittent operation is a standard feature. 239 Gas: Forced intermittent operation 0 = inactivate 1 = activated Factory settings marked with bold text. Bentone...
Page 43
After login is complete, continue with the setting work as shown below. h min s to select parameter 400 for initial commissioning and for setting air-fuel ratio control Press /reset Identification of start for setting the curve parameters. h min s Bentone...
Page 44
The value is adopted from P0. For fuel, keep depressed, for air , to adjust the value. Press h min s When symbol is no longer highlighted, the next curvepoint P2 can be selected with To the next curvepoint back to the previous curvepoint Bentone...
Page 45
If required, readjust the gas pressure. For fuel, keep depressed, for air , to adjust the value. Press h min s When symbol is no longer highlighted, the curve is set and it is possible to go on with the rest of the setting. Bentone...
Page 46
Adjust the setting downwards or upwards using the buttons h min s Press to save the setting. /reset to return to parameter level. Press Back to the previous Completing parameter parameterization of the curve Bentone...
Page 47
ESC a second When symbol time. h min s h min s The warm settings for air-fuel ratio control by the LMV37.4... are now completed. Bentone...
After login is complete, continue with the setting work as shown below. for parameter level 000. Press Press /reset Display: Parameter 050, flashes, index 00, and value 0 do not. /reset Display: Parameter bAC_UP /reset Display: Value 0 Bentone...
Page 49
If an errror occurs during the backup process, a negativ value is displayed. For error diagnostics, the cause of the error can be determined from the diagnostic code of error message 137 (see Error code list) four times until the top menu is displayed. Press Bentone...
Page 50
Display: Parameter 050, flashes, index 00, and value 0 do not. /reset Display: Parameter bAC_UP to select parameter rESstorE Press /reset Dispalay: Value 0 to select the restore process. Press /reset to shift the value in change mode 1 position to the left. Press Bentone...
Page 51
Press /reset Dispalay: 1 appears After about 8 seconds (depending on the duration of the program), 0 appears on the display, indicating the end of the backup process. Display: 0 four times until the top menu is displayed. Press Bentone...
SEr and then OPErAtE. For a list of parameters, see table 5.3.3. >5 s /reset h min s When the button is released, a change to info / service mode is made. >8 s /reset h min s Bentone...
Page 53
The unit initiates safety shutdown. The display shows current error code c: alternating with diagnostic code d:. h min s 1...3 s, to return to the normal display. Press /reset Example: Error code 12 / diagnostic code 0 h min s Bentone...
Page 54
Press .01 = error code .02 = diagnostic code .03 = error class .04 = error phase .05 = startup counter h min s .06 = output Example: Parameter 701., index 05: for startup counter, diagnostic code ._._ /reset Bentone...
Page 55
. Back to the previous index To the next index When this display appears, you have reached the end of the error history. Display – End – appears flashing. h min s Press twice. HISt 700: for error history h min s Bentone...
OFF UPr. h min s 5.7.3 Safety loop A unit whose safety loop and / or burner flange contact is open, and a controller ON signal is present, displays OFF S. h min s Bentone...
201 for selecting the operating mode. Press /reset h min s Select another burner type than the one already selected by pressing one of the buttons Confirm this selection with The automatic control unit is now reset. /reset h min s Bentone...
Manually OFF must not be used just to put a burner out of operation when doing mounting work, or when the burner is not ready for operation. The safety notes contained in chapter Safety notes must be observed! Bentone...
Connection must be done in accordance with the applicable • regulations. • Connection must conform to the wiring diagram. If any electrical connection other than that recommended by Enertech is used, there is a risk of property damage and personal injury. 172 535 09-2 Bentone...
Connect the gas line, connect the supply cable, operating and safety circuits. Before obtaining access to electrical and fuel line components all supply circuits must be disconnected. 172 515 30-2 2022-09-21 Bentone...
If leaks are found during measurement, locate the source using soapy water or leak detection spray. After sealing: check the leakage of the gas fixture again. Check for leaks in the gas line. Bentone...
The prepurge time must correspond to at least 5 complete air circulations in the fire box and adapted compartments. Calculate prepurge time using the following formula: V · 5 7.7 m · 5 150 s Q · 1.2 / 3600 770 kW · 1.2 / 3600 172 535 83 2023-03-06 Bentone...
Butan 32.25 116.09 Natural gas 29.25 Propan 24.44 88.00 Biogas 21.60 Lower calorific value H at normal conditions 15 °C and 1013 mbar, EN 676. For exact calorific value of the gas, contact the gas distributor. 172 535 82 Bentone...
For settings, see chapter LMV37. 10.3 Setting the gas damper The position of the gas damper must be adjusted to achieve the desired minimum and maximum input power. For settings, see chapter LMV37. 172 525 61-3 2023-05-10 Bentone...
Recommended air excess at basic setting Excess air flue gases% O Gas quality Natural gas 4 ±1 Propane 4 ±1 Butane 4 ±1 Liquefied petroleum gas 4 ±1 Biogas 4 ±1 Bentone...
Measure and note the lowest air pressure in the entire work area. Set the air pressure switch to about 10-15% lower than the lowest noted pressure. Test run the burner and check the function in the entire work area. Refi t protective cover. 172 525 65-2 2022-03-09 Bentone...
When the gas pressure switch stops the burner, the measured value must approximately correspond to the setting on the gas pressure switch. Open ball valve. Remove manometer and close measuring socket. Refi t protective cover. Check gas tightness. Bentone...
Set the gas pressure switch to a value 10-15% lower than the noted pressure. Test run the burner and check the function in the entire work area. Remove manometer and close measuring socket. Refi t protective cover. Check the gas tightness. Bentone...
3 Nm nominal output torque Cable length: SQM33.510… 1,5 m SQM33.511… 3,0 m Power consumption Max. 10 W Degree of protection IP54 Rated resolution encoder monitoring 0.7° Environmental conditions: Temperature range -20...+60 °C Humidity <95% r.h. 172 515 93-2 2023-05-10 Bentone...
Page 97
One-time bend when laying the cable: 2 x cable diameter • Always run the high-voltage ignition cables separate from the unit • and other cables while observing the greatest possible distance. The holding torque is reduced when the actuator is disconnected • from power. Bentone...
Gas qualities Suitable for gases of families 1, 2, 3 and other neutral gaseous media. All components must be installed without being bent, twisted or subjected to mechanical or thermal forces which can affect the components. 172 515 91-2 2022-03-23 Bentone...
Measuring connection G 1/8 connection pressure Electromagnet Measuring connection output pressure Gas pressure switch, min/VPS Measuring connection after valve 1 Electrical connection for pressure switch (possible on both sides) Gas pressure switch max Output flange Measuring connection after valve 2 Bentone...
NB This adjustment is not suitable on burners with the LMV control system with a butterfly gas valve. The adjustment of the amount of ignition gas is made here with the butterfly valve. Bentone...
Replacement upon fault detection Gas pressure switch 10 years 250,000 starts Safety blow-off system 10 years Damper motor 500,000 starts Contactor 10 years 500,000 starts The burner and its components must be recycled according to applicable regulations. 172 615 88-2 2022-09-08 Bentone...
Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. Check for leaks in the gas line. When servicing/replacing components that affect combustion, flue gas analysis and soot test must be carried out following installation. 172 615 16-2 2022-09-23 Bentone...
Fit the intake grille. Press the burner together and lock with nut (C). Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. 172 625 32 2023-02-28 Bentone...
Complete the burner assembly. Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components that affect combustion, flue gas analysis and soot test must be carried out following installation. 172 615 56-3 Bentone...
Connect the damper motor cable to the automatic control unit. Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components that affect combustion, flue gas analysis and soot test must be carried out following installation. 172 625 31-2 Bentone...
Refit the parts. Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components that affect combustion, flue gas analysis and soot test must be carried out following installation. 172 625 33 Bentone...
• Check tightness of fasteners. Check fan wheel for damage and contamination (replace if necessary). • Check motor shaft and bearings. If they are worn, replace the motor. • Use screw to attach the vibration sensor. 172 625 05 2022-09-23 Bentone...
Switch on the main power and check the operation of the new component. Start burner and check/adjust combustion. When servicing/replacing components that affect combustion, flue gas analysis and soot test must be carried out following installation. 165 105 11-3 Bentone...
Instruct the persons in charge of the operation on the service and • maintenance of the installation and what to do should any troubles occur. Inspection and service must be carried out by authorized personnel. • Review and service should be performed by authorised personnel only. 172 615 04-2 Bentone...
Voltage lower than 185V. Contact an electrician. Ignition electrodes disrupting ionisation current. Adjust ignition electrodes. Re-polarise the transformer. Poor earth connection. Ensure adequate earth connection. Phase and neutral swapped around. Check wiring diagram and change accordingly. 172 615 06 2018-01-10 Bentone...
Page 113
Flame at incorrect angle due to combustion head out of Check the combustion head and readjust. position. Condensation build up in boiler and chimney: Raise the flue gas temperature by increasing gas volume Insulate Flue gas temperature too low or gas volume too low. the chimney. Bentone...
15. Service- and inspection protocol Installation Boiler Efficiency kW: Name: Type: Address: Burner Efficiency kW: Type: Installed by: Date: Date gas/h Efficiency Governor Fluegas Ionisation Pressure temp current Fire Chimney room Measure- °C µ A ment Before After mbar mbar Small Flame Large Flame...
Page 116
UK Declaration of conformity Bentone Gas Burners Type: BFG 1 BG 400 BG 650 BG 950 STG 146 BG 450 BG 700 BG 300 BG 550 BG 800 This declaration of conformity is issued under the sole responsibility of the manufacturer.