Bentone BG 550 M LN Installation And Maintenance Instruction page 14

Table of Contents

Advertisement

3.4.5
Alarm code table
Red blinking code on
signal lamp (LED)
Blinking 2 x
••
Blinking 3 x
•••
Blinking 4 x
••••
Blinking 5 x
•••••
Blinking 6 x
••••••
Blinking 7 x
•••••••
Blinking 8 x
••••••••
Blinking 9 x
•••••••••
Blinking 10 x
••••••••••
Blinking 14 x
••••••••••••••
During the diagnosing of the alarm cause, the control outputs are voltage-
free.
The burner is disconnected.
Exception, alarm signal «AL» at board 10.
Reconnection of the burner happens after resetting only.
Press the reset button 0.5...3 s.
3.4.4
Interface diagnostics
To change to interface mode, press and hold the reset button longer than 3 s.
To go back to the normal position, press and hold the reset button longer than
3 s. If the gas burner control is in the alarm position, it is reset by pressing the
reset button 0.5...3 s.
14
Bentone
Possible causes
No flame creation at End of "TSA"
– defective or fouled flame monitoring.
– defective or fouled fuel valves.
– poor burner setting.
– defective firing device.
"LP" defective
– No air pressure switch signal after "t10".
– "LP" is welded in open position.
Illegal flame signal during start-up.
Time out "LP"
– "LP" is welded in open position.
Free
Too many flame disappearances during operation.
– poor burner setting.
– defective or fouled fuel valves.
– defective or fouled flame monitoring.
Free
Free
Connection fault or internal fault, outgoing contacts or
other faults.
CPI contact not closed.