9.2.1 List of components
A1
Gas burner control
B1
Ionization electrode
F1
Operation fuse
F2
Operation fuse
H1
Lamp, low capacity
H2
Lamp, high capacity (Optional)
K1
Motor contactor with thermal
overload protector
M1
Burner motor
M2
Damper motor, L&S
SQN75.624.A21B
S1
Operating switch

9.3 Function LME...

1.
Operating switch ON-Thermostat ON-Gas pressure switch
ON
A check that the air pressure switch does not indicate fan pressure
is carried out
2.
Burner motor starts
A check that the air pressure switch indicates sufficient fan pressure
is carried out
3.
The ignition spark is created
4.
The gas solenoid valve is open
The gas is ignited. The ionisation electrode now indicates a flame
5.
The safety time expires
The ignition spark ceases. The safety period ceases. If the spark is
missing or it disappears after this time limit, the gas burner control is
blocked
6.
Operating position
7.
Stop
The operation of the burner can now be stopped with the control
switch or thermostat
If the gas burner control is blocked
Red light in the gas burner control is lit. The burner is restarted by
pushing the reset button
9.3.1 Technical data
Preiginition time
Prepurge time
Postignition time
Safety lockout time
Reset time after lockout
Reaction time on fl ame failure
Min. ionisation current at fl ame
Max. ionisation current
S2
Operating switch, stage 2
S3
Control thermostat
S4
Temperature limiter
S5
Micro switch for hinged door
S6
Control thermostat, stage 2
S7
Main switch 3-phase
S8
Air pressure switch
S20
Main switch 1-phase
T1
Ignition transformer
X1
Connection terminal board
X2
Earth terminal
X3
Plug-in contact, burner
LME22.232C2E
3 s
20 s
2.5 s
< 3 s
< 1 s
< 1 s
5 µA
20 µA
X4
Plug-in contact, boiler
X5
Plug-in contact, stage 2,
burner
X6
Plug-in contact, stage 2 boler
X7
Plug-in contact, 3-phase,
burner
X8
Plug-in contact, 3-phase,
boiler
S9
Gas pressure switch
Y1
Gas solenoid valve 1
Y2
Gas solenoid valve 2
!
Mains connection and
fuse in accordance
with local regulations.
Bentone