4 Technical data

Model number
Short description
Interfaces
System module
General information
Cooling
B&R ID code
Status indicators
Diagnostics
Outputs
CPU function
CAN bus data transfer
RS232 data transfer
Inputs
Ethernet
I/O power supply
POWERLINK
Supply voltage monitoring
Overtemperature
Terminating resistor
Controller redundancy possible
ACOPOS support
reACTION-capable I/O channels
Visual Components support
Power consumption without interface
module and USB
Power consumption of X2X Link power
supply
1)
Power consumption
1)
Internal I/O
Additional power dissipation caused
by actuators (resistive) [W]
Type of signal lines
Certifications
CE
EAC
UL
HazLoc
ATEX
DNV GL
CPU and X2X Link power supply
Input voltage
Input current
Fuse
Reverse polarity protection
X2X Link power supply output
Nominal output power
Parallel connection
Redundant operation
Input I/O power supply
Input voltage
Fuse
Output I/O power supply
Nominal output voltage
Permissible contact load
Controller
Real-time clock
FPU
Data sheet V1.21
X20CP1301
X20cCP1301
1x RS232, 1x Ethernet, 1x USB, 1x X2X Link
0xE35B
CPU function, Ethernet, RS232, CPU power sup-
ply, I/O power supply, I/O function per channel
Digital outputs: Yes, using status LED and software (output error status)
-
Analog inputs: Yes, using status LED and software
-
-
4.3 W
Shielded cables must be used for all high-speed digital inputs/outputs, cable length: Max. 20 m
Backed up for at least 300 hours, typ. 1000 hours at 25°C, 1 s resolution, -18 to 28 ppm accuracy at 25°C
Table 3: Technical data
X20(c)CP1301, X20CP1381 and X20CP1382
X20CP1381
1x RS232, 1x Ethernet, 1x POWER-
LINK, 2x USB, 1x X2X Link, 1x CAN bus
CPU
Fanless
0xEB58
0xE35C
CPU function, Ethernet, POWERLINK, RS232,
CAN bus, CAN bus terminating resistor, CPU pow-
er supply, I/O power supply, I/O function per channel
Yes, using status LED
Yes, using status LED
Yes, using status LED
Yes, using status LED
Yes, using status LED
Yes, using software
No
Yes
No
Yes
4.8 W
0.8 W
0.8 W
-
Yes
Yes
cULus E115267
Industrial control equipment
cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
Temperature: B (0 - 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)
24 VDC -15% / +20%
Max. 1 A
Integrated, cannot be replaced
Yes
2 W
Yes
2)
Yes
3)
24 VDC -15% / +20%
Required line fuse: Max. 10 A, slow-blow
24 VDC
10 A
Yes
X20CP1382
0xDABB
Yes, using status LED
Yes, using status LED
Yes, using status LED
5.5 W
3

Advertisement

Table of Contents
loading

Related Products for BR-Automation X20CP1301

This manual is also suitable for:

X20ccp1301X20cp1381X20cp1382