3.9
Flush Mounting Bracket (L-clamp) Dimensions and Procedures
L-clamp Dimensions
3.9.1
For specific requirements, SICAM EFI is also provided with a flush mounting option on an RMU/protection
panel. This is done using a flush mounting bracket (L-clamp) (MLFB: 6MD2301-0AB00-0AA0).
The following figure shows the dimensional drawings and different views of Flush mounting bracket (L-
clamp).
[dw̲efilclampfrontviewsideview, 1, en̲US]
Figure 3-21
Device Assembly using Flush Mounting Bracket (L-clamp)
3.9.2
!
WARNING
Exercise caution when installing the device.
Non-observance of the following specified measures will result in death, severe injury, or consider-
able material damage.
Ensure AC/DC auxiliary power supply, AC BI signal, primary input to sensor and sensor output cable are
²
electrically isolated when device is under installation or maintenance.
Create an RMU panel cut-out slot of dimensions (as per Figure 3-22) and drill mounting holes at the top
²
side of the panel cut-out as per the dimensions in Figure 3-22.
SICAM, Earth Fault Indicator, Manual
E50417-H8940-C600-A3, Edition 12.2022
L-Clamp Front View and Side View
3.9 Flush Mounting Bracket (L-clamp) Dimensions and Procedures
Installation and Commissioning
45