Siemens SICAM Manual page 17

Earth fault indicator
Hide thumbs Also See for SICAM:
Table of Contents

Advertisement

Description
Ground-fault trip current range: 25 A to 100 A
Sensor ∅: 150 mm
Type 1
Sensor secondary wire length: 3.5 m or 5 m
Sensor
Used for three-core cable
Supports cable ∅ range: 60 mm to 150 mm (10 %
Accuracy)
Ground-fault trip current range: 25 A to 240 A
Sensor ∅: 140 mm
Type 2
Sensor secondary wire length: 16 m
Sensor
Used for three-core cable
Supports cable ∅ range: 90 mm to 140 mm (10 %
Accuracy)
Ground-fault trip current range: 25 A to 240 A
Sensor ∅: 280 mm
Type 3
Sensor secondary wire length: 16 m
Sensor
Used for 3 single-core cable
Supports cable pitch range: 220 mm to 340 mm
(10 % Accuracy)
Ground-fault trip current range: 25 A to 240 A
Sensor ∅: 120 mm
Type 4
Sensor secondary wire length: 16 m
Sensor
To be used for three-core cable
Supports cable ∅ range: 60 mm to 120 mm (10 %
Accuracy)
Sensor Connecting Wire Length (Refer description before ordering
sensor wire length)
3.5 m wire length is only available for
3.5 m
6MD2311-1BB00-0AA3 MLFB variant
5 m wire length is only available for
5 m
6MD2311-2BB10-0AA5 MLFB variant
16 m wire length is available for the remaining MLFB
16 m
variants.
SICAM, Earth Fault Indicator, Manual
E50417-H8940-C600-A3, Edition 12.2022