11. SNMP

This section overviews the SNMP V1 and V2c scalar and table OID-based northbound Trap and southbound GET
request functionality supported by the APM products using baseline 2.85 (and above) firmware. SNMP Community
String value configuration and supporting SNMP Managers that require non 'null' returned values is available in
baseline 2.8.3 (and above) firmware.
Scalar OID traps described in the Scalar OID Trap Objects section of this document are sent when the 'Specific Trap'
checkbox is unticked in the Configuration-Communications GUI page.
Table OID traps described in the Table OID GET Requests and Trap Objects section of this document are enabled
when the 'Specific Trap' checkbox is ticked in the Configuration-Communications GUI page.
The Antenna System Monitor (APM) SNMP Interface is defined by the following MIB files:
RF-INDUSTRIES-MIB.txt
RFI-AXM-ALARM-MIB.txt
The RFI-AXM-ALARM-MIB file provides details of the various objects (OIDs) within every trap that is sent whenever
an alarm status change occurs.
Scalar OID Trap Objects
The axmAlarmEntry object (1.3.6.1.4.1.32327.2.2.2.1.2) defines a trap and each trap includes the following 11
different objects;
axmAlarmCustName
OID 1.3.6.1.4.1.32327.2.2.2.1.2.1
Syntax
Description
axmAlarmSiteName
OID 1.3.6.1.4.1.32327.2.2.2.1.2.2
Syntax
Description
axmAlarmType
OID 1.3.6.1.4.1.32327.2.2.2.1.2.3
Syntax
Description
The possible Types (and integer values) are:
Restart (0)
SystemStatus (1)
ChannelStatus (2)
CamStatus (3)
AccessEvent (4)
IsolTestStatus (5)
Updated MIB files are available for download.
Text String
Provides the Customer Name string as configured on the User Data Configuration page.
Text String
Provides the Site Name string as configured on the User Data Configuration page.
Integer 0..5
Identifies the type of alarm that this trap relates to. The data for some of the other objects
will depend on the alarm type.
The unit has just been restarted.
The summary alarm status has changed.
An individual channel alarm status has changed.
An Alarm Module input alarm status has changed.
Three or more consecutive login attempts have failed, resulting in a lockout state.
A change in Isolation test alarm status.