APMxxxx Series User's Manual
Note:
Access to certain email addresses may be restricted by the SMTP Server being used. Emails to outside email
addresses are generally not allowed by organisations' own email servers. At this time, this SMTP Email Alarms feature
does not support the SSH authentication or encryption requirements that some email servers may require.
SNMP
SNMP Version
Selects if SNMP v1 or v2c format will be used.
Send Alarm Notifications (Traps):
Selects if sending SNMP Traps are enabled or disabled.
Specific Trap
Selects if the table OIDs will be used
Send Alarm Notifications (Traps):
Selects if sending SNMP Traps are enabled or disabled.
Specific Trap
Selects if the table OIDs will be used
SNMP GET Requests (Port 161):
Selects if Port 161 is enabled or disabled for SNMP GET requests. The default setting is 'disabled' for optimum security.
SNMP Community String:
Sets the SNMP Community String value used for both Alarm Notifications (Traps) and GET Requests. The default value is 'public'.
SNMP Manager IP Address:
Selects the IP address that SNMP notifications (Traps) will be sent to. Both a Primary and Secondary address may be used if
required for redundant SNMP server configurations.
SNMP Manager Listening Port:
Selects the port number used by the SNMP Manager. Both a Primary and Secondary address may be used if required for
redundant SNMP server configurations.
Note:
SNMP MIB files for the APM are available from RFI.
Defaults:
Clicking this button enters the factory default values for the Communications settings, which are:
DHCP
Disabled
IP Address
192.168.1.200
Subnet Mask
255.255.255.0
Gateway
192.168.1.254