Section 19 • Compressor Sequencing
Configuration Overview
Other Compressors should be configured first, and then
configure the Compressor Sequencing device table on
the compressor from user wants to start Sequencing.
The Configuration screen allows the operator to:
1. Enable Ethernet port.
2. Enable / Disable Compressor Sequencing.
3. Assign a compressor name.
4. Assign network name for sequencing.
5. Select Modbus TCP protocol.
6. Assign a unique Ethernet IP address.
Figure 19-10. Configuration Screen (Page 3) – Compressor Sequencing Setup
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3
Setting up the other Compressors for
Sequencing
1. Log onto each of the compressors one by one and
navigate to the Configuration screen see Figure
19-10.
2. Enable the Ethernet port and select the Modbus TCP
protocol.
3. Set up a unique Ethernet IP address for each
compressor.
4. Set up the Subnet Mask for the IP address.
5. Set up the Gateway address (MUST DO!).
6. Assign a Name for each compressor.
19 – 11