Section 5 • Compressor Control

Oil Control

This setpoint defines how the MicroVission will manage
the crankcase's oil. When the compressor is used in cold
climatic conditions, it might be possible that compres-
sor does not start due to low crankcase oil temperature.
Oil Crankcase Heater Temperature
When the oil temperature falls below this setpoint,
the oil heater (7th Digital Channel on Multi IO Board)
will turn ON. Note, there is a 2°F differential associ-
ated with this setpoint. For example, when set at
100 °F, the oil heater will turn ON at 98 °F and turn
OFF at 102 °F.
5 – 12
Figure 5-11. Compressor Control Screen - Oil Control
MicroVission Controller • Operation and Service Manual • Emerson • 35391MV 1.3