User Guide | Optyma™ iCO2
Terminal
Signal
Electric source
VM
Vcc
REV
VSP
Control
FG
OVERC
GND
Note: Measurement value varies depending on measurement equipment used. This value is to inspect obvious anomaly e.g. short circuit etc. and then it's not the
one to guarantee to judge right and wrong.
60 | BC408445719305en-000101
Measurement point
Between 1pin and 2pin of power source terminal (GND)
Between 1pin and 2pin of power source terminal (GND)
Between 2pin and 2pin of power source terminal (GND)
Between 3pin and 2pin of power source terminal (GND)
Between 4pin and 2pin of power source terminal (GND)
Between 5pin and 2pin of power source terminal (GND)
Between 6pin and 2pin of power source terminal (GND)
Part number for fanm otor
Red-Black
White-Black
Orange-Black
Yellow-Black
Blue-Black
Green-Black
Peach-Black
© Danfoss | Climate Solutions | 2023.01 | LCA012A030
SSA512T101 or
SSA512T155
1MΩ and over
7.7kΩ ±20%
1MΩ and over
200k Ω ±10%
1MΩ and over
1MΩ and over
1MΩ and over