Installation, Operation and
MicroChannel Heat Exchangers
Maintenance Manual
MCHE
Installation and Maintenance Guide
APP pumps (APP 21-43)
ro-solutions.com
www.danfoss.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MicroChannel Heat Exchanger and is the answer not in the manual?

Questions and answers

Summary of Contents for Danfoss MicroChannel Heat Exchanger

  • Page 1 Service guide User manual Installation, Operation and MicroChannel Heat Exchangers Maintenance Manual MCHE Installation and Maintenance Guide APP pumps (APP 21-43) ro-solutions.com www.danfoss.com...
  • Page 2: Table Of Contents

    Sevice guide | Application, Installation and Maintenance Manual MCHE Table of Contents Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Introduction .
  • Page 3: Introduction

    Indicates something to be noted by the carefully before commencing any work . reader Danfoss is not responsible or liable for any damage caused by failure to comply with the instructions in this manual and/or due to Indicates a situation which will or could...
  • Page 4: Storage And Working Environments

    Table 1 for different microchannel tubes and fins . Consult with Danfoss for the tubes not listed . Do not arbitrarily extrapolate or interpolate the values . Fig . 1 Handling attentions Structural parameters Min .
  • Page 5: Installation

    Few tubes Fig . 3 Fan location and size Fig . 2 MCHE passes distribution Danfoss MCHEs include a small notch in both headers to indicate that this is the bottom of the heat exchanger . Additionally, a product label is...
  • Page 6: Coil Mounting Against Thermal Expansion

    Sevice guide | Application, Installation and Maintenance Manual MCHE 3.3 Coil mounting against thermal expan- sion Thermal expansion of aluminum is higher than most other metals . Frequent thermally induced stress could shorten the life of the micro channel heat exchanger (Fig .4) Allow it to move 50 K Allow it to move...
  • Page 7: Elimination Of Gaps

    Service guide | Application, Installation and Maintenance Manual MCHE Plastic heat shrink tubing prevents galvanic corrosion in the MCHE’s copper to aluminum joint by keeping moisture from entering the area . A minimum of 70mm length from the Cu/Al joint to the connection point is required to protect the Cu-Al brazing joint and plastic shrink tube from excessive heat during the brazing process .
  • Page 8: Vibration

    Fig . 10b Rubber support Leak repair is not practical to repair a MCHE refrigerant leak in the field . Danfoss recommends replacement of the MCHE in the event that a leak develops It due to a defect, mechanical damage or prema- ture corrosion .
  • Page 9: Coating

    & fin coil fins but still need to be handled with care . Do not hit the coil with Danfoss recommends the use of air filters on the the hose . We recommend placing your thumb frontal face of the MCHE to lower the deposition...