User Guide | Optyma™ iCO2
(2) Load unit side
Connect a PC to the condensing unit and check the operation status of the load unit side unit using the mente-PC software.
Item with* 3 can also be possible to check from the each Evaporator Controller. See literature of User Guide Controller for appliance control AK-CC55.
Cooler 1: Roomtemperature SV
Cooler 1: Roomtemperature PV
Cooler 1: superheat SV
Cooler 1: superheat PV
Cooler 1: expansion valve opening duty
Cooler 1: information
Cooler 1: Liquid feeding solenoid valve
Cooler 1: defrost status
Cooler 1: fan Operating
Cooler 2: Roomtemperature SV
Cooler 2: Roomtemperature PV
Cooler 2: superheat SV
Cooler 2: superheat PV
Cooler 2: expansion valve opening duty
Cooler 2: information
Cooler 2: Liquid feeding solenoid valve
Cooler 2: defrost status
Cooler 2: fan Operating
Cooler 3: Roomtemperature SV
Cooler 3: Roomtemperature PV
Cooler 3: superheat SV
Cooler 3: superheat PV
Cooler 3: expansion valve opening duty
Cooler3: information
Cooler 3: Liquid feeding solenoid valve
Cooler 3: defrost status
Cooler 3: fan Operating
Cooler 4: Roomtemperature SV
Cooler 4: Roomtemperature PV
Cooler 4: superheat SV
Cooler 4: superheat PV
Cooler 4: expansion valve opening duty
Cooler 4: information
Cooler 4: Liquid feeding solenoid valve
Cooler 4: defrost status
Cooler 4: fan Operating
Cooler 5: Roomtemperature SV
Cooler5:Roomtemperature PV
Cooler5:superheat SV
Cooler5:superheat PV
Cooler5:expansion valve opening duty
Cooler5:information
Cooler5:Liquid feeding solenoid valve
Cooler5:defrost status
Cooler5:fan Operating
40 | BC408445719305en-000101
Display
*3 (r00)
*3 (u36)
*3 (u22)
*3 (u21)
*3 (u23)
*3 (u60)
*3 (u59)
*3 (r00)
*3 (u36)
*3 (u22)
*3 (u21)
*3 (u23)
*3 (u60)
*3 (u59)
*3 (r00)
*3 (u36)
*3 (u22)
*3 (u21)
*3 (u23)
*3 (u60)
*3 (u59)
*3 (r00)
*3 (u36)
*3 (u22)
*3 (u21)
*3 (u23)
*3 (u60)
*3 (u59)
*3 (r00)
*3 (u36)
*3 (u22)
*3 (u21)
*3 (u23)
*3 (u60)
*3 (u59)
Unit
Criteria
°C
-45~30
°C
-45~30
deg
>5
deg
>5
%
0~100
-
-
ON(1)/OFF(0)
-
ON(1)/OFF(0)
-
ON(1)/OFF(0)
-
°C
-45~30
°C
-45~30
deg
>5
deg
>5
%
0~100
-
-
ON(1)/OFF(0)
-
ON(1)/OFF(0)
-
ON(1)/OFF(0)
-
°C
-45~30
°C
-45~30
deg
>5
deg
>5
%
0~100
-
-
ON(1)/OFF(0)
-
ON(1)/OFF(0)
-
ON(1)/OFF(0)
-
°C
-45~30
°C
-45~30
deg
>5
deg
>5
%
0~100
-
-
ON(1)/OFF(0)
-
ON(1)/OFF(0)
-
ON(1)/OFF(0)
-
°C
-45~30
°C
-45~30
deg
>5
deg
>5
%
0~100
-
-
ON(1)/OFF(0)
-
ON(1)/OFF(0)
-
ON(1)/OFF(0)
-
© Danfoss | Climate Solutions | 2023.01 | LCA012A030