Default Dip Switch Settings - Veris Industries E31 Series Installation Manual

Branch circuit power meter with split-core cts
Table of Contents

Advertisement

E31 Series Installation Guide
Configuration (cont.)
Default DIP
Switch Settings
Z205667-0G
Page 19 of 23
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
3. The E31 uses two logical addresses. Panel 1 uses the base address as set on the DIP switches, and Panel 2 uses this base address
+ 1. Address the E31 as any whole number between and including 1-246. Each unit is equipped with a set of 8 DIP switches for
addressing. See below.
LSB
1
2
4
8
4. To determine an address, simply add the values of any switch that is on.
For example:
LSB
Switch number 4 has an ON Value of 8 and switch number 6 has an ON Value of 32. (8 + 32 = 40). Therefore, the address for
Panel 1 is 40, and the address for Panel 2 is 41.
See the Address Setup section for a pictorial listing of the first 63 switch positions.
The E31 includes two DIP switches, as shown below. Switches are shown in their default positions.
Comms Address
©2015 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
1
=
MSB
DIP Switch Values
16
32
64
128
40
=
MSB
Comms Settings
TM
0815