Bacnet Default Settings - Veris Industries E51H2A Installation Manual

Bi-directional compact power and energy meter with bacnet ms/tp support for use only with e683 series rope cts
Table of Contents

Advertisement

Installation Guide
Power Monitoring
BACnet Default
Settings
ZL0123-0D
Page 19 of 32
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Setting
Setup Password
Reset Password
System Type
CT Primary Ratio
PT Ratio
System Voltage
Max. Theoretical Power
Display Mode
Phase Loss Voltage Threshold
Phase Loss Voltage Threshold
Demand: number of subintervals per interval
Demand: sub-interval length
BACnet MAC Address
BACnet MS/TP Baud Rate
BACnet MS/TP Max_Master
BACnet Device_ID
BACnet Device Location
Trend_Log Object 1
Log_Device_Object_Property **
Trend_Log Object 2
Log_Device_Object_Property **
Trend_Log Object 3
Log_Device_Object_Property **
* Default values are preset at the factory. Once changed, there is no way to automatically reset defaults. They must be restored individually. The baud rate and
MAC address are set through the user-interface screens, and the others are set by re-writing each Object (see BACnet Programming Information section).
** These values are available only on the E51H5A. The E51H2A does not support the data logging functions.
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Default Value*
00000
00000
40 (3 + N) Wye
100A
1:1 (none)
600 V L-L
Calculated from AV2, AV3, AV5 & AV6 (with all default
settings, this would be 103.92 kW)
1 (IEEE Units)
10% of System Voltage
25% Phase to Phase Imbalance
1 (block mode)
900 sec (15 min)
(AV11 default value is 90000 [1/100 seconds])
001
76.8 kBaud
127
Pseudo-random value
from 1,000,000 to 3,097,151
Installed location not yet identified
AI2 (Real Energy Import)
AI3 (Real Energy Export)
AI19 (Total Real Power Present Demand)
TM
BACnet Object
n/a
n/a
AV2
AV3
AV5
AV6
AI45
AV7
AV8
AV9
AV10
AV11
n/a
n/a
Device
Device
Device
TL1
TL2
TL3
0818