E31 Series Installation Guide
Installation (cont.)
Z205667-0G
Page 13 of 23
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
6. Plastic cable ties are included with the product for strain relief. Insert the strain relief device into one of the available holes on
the adapter board (Figure 6A). Gather all current sensor wires connected to that adapter board and secure the cable tie around
them (Figure 6B).
Figure 6
(A)
7. The adapter boards are silk screened with two rows of numbers. For applications that require odd/even branch circuit
numbering, use the row designated ODD or EVEN. For applications that require sequential numbering, use the number row
marked SEQ (Figure 7, 8).
Figure 7
BLACK
WHITE
ODD
SEQ
Adapter Board A numbering:
ODD
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41
SEQ
21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
BLACK
WHITE
EVEN
SEQ
Adapter Board B numbering:
EVEN
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
SEQ
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
©2015 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.