E31 Series Installation Guide
Specifications
Z205667-0G
Page 3 of 23
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Measurement Voltage
Control Power
Power/Energy
Sampling Frequency
Update Rate
Overload Capability
Communication Format
Termination
Aux CT Terminals on Main Board
Removable Connectors on Main Board
Terminals on CT Adapter Boards
Aux CT Terminals on Main Board
Removable Connectors on Main Board
Terminals on Branch CT Adapter Boards
Ribbon Cable Support
Operating Temperature Range
Storage Temperature Range
Altitude of Operation
Agency Approvals
Installation Category
Conducted and Radiated Emissions
Conducted and Radiated Immunity
* See Configuration section for details.
**The E31 must be installed in an appropriate electrical and fire enclosure per local regulations. If Veris E31 products are used in
installations with circuits higher than the product ratings, the circuits must be kept segregated per UL508A Sec. 17.5. Note: E31
internal circuitry (cables and CTs) are not circuits as defined by UL508A, as they do not extend beyond the E31 itself without further
safety/fire isolation.
*** A Pollution Degree 2 environment must control conductive pollution and the possibility of condensation or high humidity.
Consideration must be given to the enclosure, the correct use of ventilation, thermal properties of the equipment and the
relationship with the environment.
©2015 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
VOLTAGE INPUTS
90 to 300 Vac line-to-neutral, 50/60 Hz
90 to 277 Vac line-to-neutral, 50/60 Hz
ACCURACY
IEC 62053-21 Class 1, ANSI C12.1-2008 system accuracy (including 50 A or
100 A branch CTs)
Voltage
±0.5% of reading 90 to 277 V line-to-neutral
OPERATION
2560 Hz
1.8 seconds (both panels)
22 kAIC
OUTPUTS
Type
Modbus RTU
Connection
DIP switch-selectable 2-wire or 4-wire, RS-485
Address
DIP switch-selectable address 1 to 247 (in pairs of 2)*
Baud Rate
DIP switch-selectable 9600, 19200, 38400
Parity
DIP switch-selectable NONE, ODD, EVEN
8 data bits, 1 start bit, 1 stop bit
5-position depluggable connector
(TX+ TX- SHIELD TX+/RX+ TX-/RX-)
WIRE SIZE RANGE
24 to 14 AWG
22 to 12 AWG
26 to 16 AWG
TERMINAL BLOCK TORQUE
3.5 to 4.4 in-lb (0.4 to 0.5 N-m)
4.4 to 5.3 in-lb (0.5 to 0.6 N-m)
1.9 to 2.2 in-lb (0.22 to 0.26 N-m)
MECHANICAL
4 ft. (0.9 m) round ribbon cable ships standard; up to 20 ft. (6 m) flat or
round available
OPERATING CONDITIONS
0 to 60 °C (32 to 140 °F) (<95% RH non-condensing)
-40 to 70 °C (-40 to 158 °F)
3000 m
COMPLIANCE INFORMATION
UL508 open type device**, IEC/EN61010-1
Cat III, pollution degree 2***
FCC part 15 Class B, EN55011/EN61000-6-3 Class B (residential and light
industrial)
EN 61000-6-2 and EN 61326-1
TM
0815