Bacnet Default Settings - Veris Industries E50H Series Installation Manual

Compact power and energy meters with bacnet ms/tp support
Table of Contents

Advertisement

E50H2, E50H5 Installation Guide
BACnet Default
Settings
ZL0071-0F
Page 17 of 28
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Setting
Setup Password
00000
Reset Password
00000
System Type
40 (3 + N) Wye
CT Primary Ratio
100A
CT Secondary Ratio
1V
PT Ratio
1:1 (none)
System Voltage
600 V L-L
Max. Theoretical Power
Calculated from AV2, AV3, AV5 & AV6 (with all default settings, this would be
103.92 kW)
Display Mode
1 (IEEE Units)
Phase Loss Voltage Threshold 10% of System Voltage
Phase Loss Voltage Threshold 25% Phase to Phase Imbalance
Demand: number of
1 (block mode)
subintervals per interval
Demand: sub-interval length 900 sec (15 min)
(AV11 default value is 90000 [1/100 seconds])
BACnet MAC Address
001
BACnet MS/TP Baud Rate
76.8 kBaud
BACnet MS/TP Max_Master
127
BACnet Device_ID
Pseudo-random value
from 1,000,000 to 3,097,151
BACnet Device Location
Installed location not yet identified
Trend_Log Object 1
AI1 (Real Energy)
Log_Device_Object_
Property **
Trend_Log Object 2
AI27 (Reactive Energy)
Log_Device_Object_
Property **
Trend_Log Object 3
AI34 (Total Real Present Demand)
Log_Device_Object_
Property **
* Default values are preset at the factory. Once changed, there is no way to automatically reset defaults. They must be restored individually. The baud rate and
MAC address are set through the user-interface screens, and the others are set by re-writing each Object (see BACnet Programming Information section, next
page).
** These values are available only on the E50H5. The E50H2 does not support the data logging functions.
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
Default Value*
TM
BACnet Object
n/a
n/a
AV2
AV3
AV4
AV5
AV6
AI45
AV7
AV8
AV9
AV10
AV11
n/a
n/a
Device
Device
Device
TL1
TL2
TL3
0818

Advertisement

Table of Contents
loading

This manual is also suitable for:

E50h2E50h5

Table of Contents