Standard Modbus Default Settings - Veris Industries E50C1A Installation Manual

Compact power and energy meter for use only with e683 series rope cts
Table of Contents

Advertisement

E50C1A Installation Guide
RS-485
Communications
Standard Modbus
Default Settings
ZL0124-0E
Page 15 of 20
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Daisy-chaining Devices to the Power Meter
The RS-485 slave port allows the power meter to be connected in a daisy chain with up to 63 2-wire devices.
120 Ω terminator on the first and last
device of the daisy chain
+
S
Shield wire
Notes
• The terminal's voltage and current ratings are compliant with the requirements of the EIA RS-485 communications
standard.
• The RS-485 transceivers are ¼ unit load or less.
• RS-485+ has a 47 kΩ pull up to +5V, and RS-485- has a 47 kΩ pull down to Shield (RS-485 signal ground).
• Wire the RS-485 bus as a daisy chain from device to device, without any stubs. Use 120 Ω termination resistors at each
end of the bus (not included).
• Shield is not internally connected to Earth Ground.
• Connect Shield to Earth Ground somewhere on the RS-485 bus.
For all terminals:
• When tightening terminals, apply the correct torque: 0.37 to 0.44
ft·lb (0.5-0.6 N·m).
• Use 14-24 gauge (2.1-0.2 mm
Setting
Setup Password
Reset Password
System Type
CT Primary Ratio (if CTs are not included)
CT Secondary Ratio
PT Ratio
System Voltage
Max. Theoretical Power
(Analog Output: full scale (20mA or 5V))
Display Mode
Phase Loss
Pulse Energy
Modbus Address
Modbus Baud Rate
Modbus Parity
©2018 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
2
) wire.
00000
00000
40 (3 + N) Wye
100A
1V
1:1 (none)
600 V L-L
104 kW
1 (IEEE)
10% of System Voltage (60V), 25% Phase to Phase Imbalance
1 (kWh/pulse)
001
19200 baud
None
0.37 to 0.44 ft-lb
(0.5 to 0.6 N-m)
Value
TM
Use 14 to 24 ga
Modbus
Register
130
131
132
133
134
135
137
142, 143
144
0818