5 .6 Coa x ia l Vent ing I nst ruct ions
Maximum equivalent flue lengths for Coaxial venting
are:
Coa x ia l Pipe Ve n t Le n gt h s
( Includes First Elbow And Termination)
Boile r
7 5 / 1 0 0 / 1 1 5
Size
1 2 5 / 1 5 0
4" / 2"
Ve n t Size
[ 100m m / 60m m ]
32.8 ft [ 10m ]
Natalini
DuraVent
27.88 ft [ 8.5m ]
Centrotherm 24.60 ft [ 7.5m ]
Z-Flex/ Z-
24.60 ft [ 7.5m ]
Dens
Coa x ia l Elbow s - Equ iva le n t le n gt h
4" / 2" [ 100 m m / 60 m m ]
45°
90°
5" / 3" [ 128 m m / 80 m m ]
45°
90°
Coaxial Term inat ion - Equivalent lengt h 3 ft ( 0.9m )
NOTE:
Coaxial vent ing can run horizont al or vert ical.
• Connect flue elbow to top of boiler and adjust direction
of elbow t o desired orient at ion ( rear, right or left ) .
• Measure dist ance from out side wall face t o elbow, t his
dim ension will be known as 'X" , add dist ance " Y" + 2"
( 60 m m ) t o " X" t his is t he t ot al dim ension of t he vent s.
See Figure 5- 2.
• Mark dim ension from above on out er alum inum int ake
vent . Measure lengt h of wast e m at erial, and t ransfer
dimension to inner grey flue pipe.
• Remove waste from both vents (flue and air). Verify cut
ends are square and free from burrs. Insert flue back
int o int ake air vent and pass t hem t hrough hole in wall.
• Check all m easurem ent s before cut t ing. Clearance t o
com bust ible m at erials is zero when using coaxial vent
syst em .
• Aft er inst alling vent ing use calibrat ed analyzer t o verify
t here is no recirculat ion of com bust ion.
• Ensure Horizont al t erm inat ion is posit ioned wit h fresh air
slot s on t he bot t om .
5 - COM BU STI ON AI R AN D V EN T PI PI N G
1 6 5 / 2 0 5
5" / 3"
[ 128m m / 80m m ]
M a x im u m
32.8 ft [ 10m ]
1.64 ft. [ 0.5 m ]
3.28 ft. [ 1.0 m ]
1.64 ft. [ 0.5 m ]
3.28 ft. [ 1.0 m ]
Asphyxiat ion hazard! Before securing screws
ensure t he pipe has been pushed in a m inim um
of 1- 3/ 4" ( 45 m m ) int o t he gasket end of t he
ot her pipe. Failure t o follow t hese inst ruct ions
could result in deat h or serious inj ury.
ALL
ALL
M inim um
6 ft .
[ 1.8m ]
WT = Wall Thickness
Not e: 2" is insert ion dept h of st raight pipe t o elbow.
1.97 in ( 50 m m )
1.97 in ( 50 m m )
2 1
!
W ARN I N G
2"
240013503 REV A, [ 03/ 15/ 2022]
2"
m in. 7.09 in ( 180 m m )
m in. 7.09 in ( 180 m m )
m ax. 13.78 in ( 350 m m )
m ax. 13.78 in ( 350 m m )